FIR04-00184
| INSP-Final Inspection | 7/26/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | FAIL |
|
|
was only able to complete buildings 4 and 8 today. 7/28/2004 11:26:51 AM
|
BLD03-01809
| FIRE-Final Inspection | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | FAIL |
|
|
Need one additional emergency light at the courtyard exit corridor. 7/28/2004 10:45:15 AM
|
FIR04-00420
| INSP-Sprinkler Rough-in | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | PASS |
|
|
sprinkler piping is ok to cover 7/28/2004 12:12:52 PM
|
FIR04-00420
| INSP-Final Inspection | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | FAIL |
|
|
need ceiling tile and canopies for final 7/28/2004 12:13:13 PM
|
FIR04-00250
| INSP-Final Inspection | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | P | FAIL |
|
|
Syncronize strobes. See review note #7. Provide temporal for horns. See review note #6. Provide map for the facp per review note #3. 7/28/2004 4:07:10 PM
|
BLD03-01840
| FIRE-Final Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 7/28/2004 3:51:43 PM
|
BLD03-01809
| FIRE-Final Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety and fire alarm finaled. The fire alarm permit will be left open until contractor resubmitts drawings with revised scope of work 7/28/2004 2:00:30 PM
|
BLD04-00988
| FIRE-Final Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | P | FAIL |
|
|
Remove thumbturn from the main entry/exit. Keyed both sides is ok. See review note #5. Provide annual inspection for the fire extinguisher. See review note #4. Remove key locking hardware from the south exit. Provide "Door to remain unlocked while building is occupied" sticker at the main entry/exit. Provide annunciator for the duct smoke detector per IMC 606.4.1 exception #2 then test detector. Provide hardware on the gated area for inspection. 7/28/2004 3:55:13 PM
|
FIR03-00647
| INSP-Conference | 7/28/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | P | DONE |
|
|
Fire alarm inspection for phases 1 and 2 are complete. The fire alarm contractor to resubmit drawings showing what work has been completed and then resubmit drawings for each additional phase that requires a building permit
|
FIR04-00250
| INSP-Final Inspection | 7/27/2004 | 7/28/2004 | 7/27/2004 3:23:51 PM | A | CANC |
|
|
Please Call the office one hour befor inspection if possiable. Thank you Terry; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|