Inspections for the day of: Wednesday, July 28, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00184 INSP-Final Inspection7/26/20047/28/20047/28/2004 12:00:00 AMAFAIL
was only able to complete buildings 4 and 8 today. 7/28/2004 11:26:51 AM
BLD03-01809 FIRE-Final Inspection7/27/20047/28/20047/28/2004 12:00:00 AMAFAIL
Need one additional emergency light at the courtyard exit corridor. 7/28/2004 10:45:15 AM
FIR04-00420 INSP-Sprinkler Rough-in7/27/20047/28/20047/28/2004 12:00:00 AMAPASS
sprinkler piping is ok to cover 7/28/2004 12:12:52 PM
FIR04-00420 INSP-Final Inspection7/27/20047/28/20047/28/2004 12:00:00 AMAFAIL
need ceiling tile and canopies for final 7/28/2004 12:13:13 PM
FIR04-00250 INSP-Final Inspection7/27/20047/28/20047/28/2004 12:00:00 AMPFAIL
Syncronize strobes. See review note #7. Provide temporal for horns. See review note #6. Provide map for the facp per review note #3. 7/28/2004 4:07:10 PM
BLD03-01840 FIRE-Final Inspection7/28/20047/28/20047/28/2004 12:00:00 AMPPASS
Fire life safety finaled 7/28/2004 3:51:43 PM
BLD03-01809 FIRE-Final Inspection7/28/20047/28/20047/28/2004 12:00:00 AMPPASS
Fire life safety and fire alarm finaled. The fire alarm permit will be left open until contractor resubmitts drawings with revised scope of work 7/28/2004 2:00:30 PM
BLD04-00988 FIRE-Final Inspection7/28/20047/28/20047/28/2004 12:00:00 AMPFAIL
Remove thumbturn from the main entry/exit. Keyed both sides is ok. See review note #5. Provide annual inspection for the fire extinguisher. See review note #4. Remove key locking hardware from the south exit. Provide "Door to remain unlocked while building is occupied" sticker at the main entry/exit. Provide annunciator for the duct smoke detector per IMC 606.4.1 exception #2 then test detector. Provide hardware on the gated area for inspection. 7/28/2004 3:55:13 PM
FIR03-00647 INSP-Conference7/28/20047/28/20047/28/2004 12:00:00 AMPDONE
Fire alarm inspection for phases 1 and 2 are complete. The fire alarm contractor to resubmit drawings showing what work has been completed and then resubmit drawings for each additional phase that requires a building permit
FIR04-00250 INSP-Final Inspection7/27/20047/28/20047/27/2004 3:23:51 PMACANC
Please Call the office one hour befor inspection if possiable. Thank you Terry; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley