Inspections for the day of: Thursday, July 28, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02483 Final7/28/20057/28/20057/28/2005 4:18:37 PMPNR
reinspection for final.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH Talked to contr, need field evaluation to inspect. typ for cell sites.
ELE05-02482 Final7/28/20057/28/20057/28/2005 4:15:57 PMPNR
Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH Talked to contr., need field evaluation to inspect installation. typ at cell sites.
ELE05-01909 Final7/28/20057/28/20057/28/2005 2:21:21 PMPPART
Scheduled by a contractor via Hello! on 7/28/2005 at 9:20:11 AM. Contact: ###-####. all but recpts in big room ok. elect will do some ckt tracing and call back.
ELE05-01835 Final7/28/20057/28/20057/28/2005 2:19:33 PMPPASS
Final inspection on gargae; Phone #: ###-#### Internet Inspection Request from: William Zerfas called to have blank cover put on over gec connection. ok to final
ELE05-02626 Final7/28/20057/28/20057/28/2005 1:59:20 PMPCANC
alex or mat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see ps
ELE05-02691 Permanent Service7/27/20057/28/20057/28/2005 10:41:46 AMANR
Phone #: ###-#### Internet Inspection Request from: Therrin called contr, will call after gec poured
ELE05-02543 Final7/27/20057/28/20057/28/2005 10:40:41 AMANH
Scheduled by a contractor via Hello! on 7/27/2005 at 3:26:02 PM. Contact: ###-####. called contr, left card.
ELE05-02691 Electrical Rough-In7/27/20057/28/20057/28/2005 10:25:13 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ric ok
ELE05-02210 Electrical Rough-In7/27/20057/28/20057/28/2005 10:24:26 AMACANC
Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH see rip
ELE05-02634 Electrical Rough-In7/27/20057/28/20057/28/2005 9:01:01 AMAPASS
inspect the ufer ground for cover; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover gec
ELE05-02706 Rough-In Permanent Service7/27/20057/28/20057/28/2005 8:57:16 AMAPASS
brian ###-#### ric ok p/s u/g n ok
ELE05-00768 Final7/27/20057/28/20057/28/2005 8:51:23 AMAFAIL
Final inspect on new construction; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice 352.39(A) rnc shall be strapped within 3' of box, 210.8(A)(2) garage recpts shall be gfci protected,210.52(D) recpt shall be within 3' of bath sink
ELE05-00842 Final7/28/20057/28/20057/28/2005 8:33:15 AMAPASS
Scheduled by a contractor via Hello! on 7/28/2005 at 6:58:53 AM. Contact: ###-####. called contr to put in gnd screw in bath, corrections made. ok to final
ELE05-02215 Electrical Rough-In7/27/20057/28/20057/28/2005 8:30:19 AMANR
Pole base inspection.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr to finish piping
ELE05-02210 Rough-In Permanent Service7/28/20057/28/20057/28/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ric ok, p/s u/g n ok
ELE05-02626 Permanent Service7/28/20057/28/20057/28/2005 12:00:00 AMPPASS
alex or mat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for power, called contr to provide abrasion protection for gec, they are coming to move fence. p/s u/g n ok