ELE05-02483
| Final | 7/28/2005 | 7/28/2005 | 7/28/2005 4:18:37 PM | P | NR |
|
|
reinspection for final.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH Talked to contr, need field evaluation to inspect. typ for cell sites.
|
ELE05-02482
| Final | 7/28/2005 | 7/28/2005 | 7/28/2005 4:15:57 PM | P | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH Talked to contr., need field evaluation to inspect installation. typ at cell sites.
|
ELE05-01909
| Final | 7/28/2005 | 7/28/2005 | 7/28/2005 2:21:21 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 7/28/2005 at 9:20:11 AM. Contact: ###-####. all but recpts in big room ok. elect will do some ckt tracing and call back.
|
ELE05-01835
| Final | 7/28/2005 | 7/28/2005 | 7/28/2005 2:19:33 PM | P | PASS |
|
|
Final inspection on gargae; Phone #: ###-#### Internet Inspection Request from: William Zerfas called to have blank cover put on over gec connection. ok to final
|
ELE05-02626
| Final | 7/28/2005 | 7/28/2005 | 7/28/2005 1:59:20 PM | P | CANC |
|
|
alex or mat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see ps
|
ELE05-02691
| Permanent Service | 7/27/2005 | 7/28/2005 | 7/28/2005 10:41:46 AM | A | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin called contr, will call after gec poured
|
ELE05-02543
| Final | 7/27/2005 | 7/28/2005 | 7/28/2005 10:40:41 AM | A | NH |
|
|
Scheduled by a contractor via Hello! on 7/27/2005 at 3:26:02 PM. Contact: ###-####. called contr, left card.
|
ELE05-02691
| Electrical Rough-In | 7/27/2005 | 7/28/2005 | 7/28/2005 10:25:13 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ric ok
|
ELE05-02210
| Electrical Rough-In | 7/27/2005 | 7/28/2005 | 7/28/2005 10:24:26 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH see rip
|
ELE05-02634
| Electrical Rough-In | 7/27/2005 | 7/28/2005 | 7/28/2005 9:01:01 AM | A | PASS |
|
|
inspect the ufer ground for cover; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover gec
|
ELE05-02706
| Rough-In Permanent Service | 7/27/2005 | 7/28/2005 | 7/28/2005 8:57:16 AM | A | PASS |
|
|
brian ###-#### ric ok p/s u/g n ok
|
ELE05-00768
| Final | 7/27/2005 | 7/28/2005 | 7/28/2005 8:51:23 AM | A | FAIL |
|
|
Final inspect on new construction; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice 352.39(A) rnc shall be strapped within 3' of box, 210.8(A)(2) garage recpts shall be gfci protected,210.52(D) recpt shall be within 3' of bath sink
|
ELE05-00842
| Final | 7/28/2005 | 7/28/2005 | 7/28/2005 8:33:15 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/28/2005 at 6:58:53 AM. Contact: ###-####. called contr to put in gnd screw in bath, corrections made. ok to final
|
ELE05-02215
| Electrical Rough-In | 7/27/2005 | 7/28/2005 | 7/28/2005 8:30:19 AM | A | NR |
|
|
Pole base inspection.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr to finish piping
|
ELE05-02210
| Rough-In Permanent Service | 7/28/2005 | 7/28/2005 | 7/28/2005 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ric ok, p/s u/g n ok
|
ELE05-02626
| Permanent Service | 7/28/2005 | 7/28/2005 | 7/28/2005 12:00:00 AM | P | PASS |
|
|
alex or mat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for power, called contr to provide abrasion protection for gec, they are coming to move fence. p/s u/g n ok
|