Inspections for the day of: Thursday, July 28, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00976 FIRE-Conference7/28/20057/28/20057/28/2005 4:13:52 PMPDONE
On site discussion with Kent the GC regarding duct smoke detection, remote annunciators, egress lighting, building address, door hardware and location of fire extinguishers.
FIR05-00419 INSP-Final Inspection7/28/20057/28/20057/28/2005 4:10:48 PMPPART
Overhead fire sprinkler rough-in is good for cover, will final permit when protective caps are removed from heads and ceiling tile with escutcheons are installed.
FIR05-00190 INSP-Conference7/28/20057/28/20057/28/2005 3:33:51 PMPCANC
Inspection is re-scheduled for tomorrow a.m per Phil Doble.
BLD05-01435 FIRE-Final Inspection7/28/20057/28/20057/28/2005 2:35:49 PMPPASS
Fire extinguisher has been moved to a normal path of travel. Fire life safety finaled.
FIR05-00422 INSP-Sprinkler Rough-in7/28/20057/28/20057/28/2005 2:29:06 PMPFAIL
Minimum spacing requirements for the installed residential heads in storage room 103, bathroom closet 207, and master bedroom 201 are not met as required, (see plan review note #17).
MIS05-00070 MIS-Aging Inspection7/28/20057/28/20057/28/2005 12:00:00 AMAFAIL
Provide sign above main entry/exit stating "this door to remain unlocked while building is occupied", provide approved hardware and remove thumbturn at door from garage area at south side, provide lever hardware at restroom door.
FIR05-00374 INSP-Final Inspection7/28/20057/28/20057/28/2005 12:00:00 AMPPASS
Permit is finaled.
FIR04-00730 INSP-Final Inspection7/28/20057/28/20057/28/2005 12:00:00 AMPPASS
Fire alarm finaled.
FIR04-00593 INSP-Final Inspection7/28/20057/28/20057/28/2005 12:00:00 AMPPASS
Fire sprinkler permit finaled.
BLD04-00896 FIRE-Final Inspection7/28/20057/28/20057/28/2005 12:00:00 AMPPASS
Fire life safety passed inspection.