Inspections for the day of: Thursday, July 28, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00586 FIR-Aging Inspection7/28/20057/28/20058/1/2005 3:24:20 PM NR
Per Brian with AIC he will contact the owner again to provide the knox key box.
FIR04-00004 FIR-Aging Inspection7/28/20057/28/20058/1/2005 1:59:22 PM NR
Jim Danes is not sure that the work has been done. He will verify.
FIR05-00210 FIR-Aging Inspection7/28/20057/28/20058/1/2005 1:51:58 PM NR
I left a message on Ridgeway Mechanicals answering machine requesting status of job from John or Earl. Construction is still in progress at the job site.
BLD05-01222 FIRE-Sprinkler Rough-in7/28/20057/28/20057/28/2005 3:55:52 PMPFAIL
bill ###-####. Provide sticker at the main exit. provide fire extinguishers. Provide door hardware on the double doors to the stockroom. Provide approved door hardware on the new east exit door and remove the deadbolt.
BLD05-00660 FIRE-Conference7/28/20057/28/20057/28/2005 3:53:20 PMPPASS
Inspection was for viewing some of the treated wood. It appears to be treated per the example presented.
FIR05-00124 INSP-Sprinkler Rough-in/Hydro7/27/20057/28/20057/28/2005 3:50:51 PMPPART
contact dave. 24 hr air test.; Starting pressure at just above 43psi at 12:00
FIR04-00737 INSP-Sprinkler Rough-in/Hydro7/27/20057/28/20057/28/2005 3:50:22 PMPPART
contact dave. 24 hr air test.; Starting pressure at just above 42psi at 12:00
BLD05-01566 FIRE-Conference7/27/20057/28/20057/28/2005 1:30:27 PMAFAIL
jeremy --; Phone #: ###-#### Provide two fire extinguishers as discussed. See review note #2. Also provide fire extinguisher in mezzanine. Provide emergency lights and exit signs as shown on A1.0. Provide approved door hardware on the rest room doors. Provide panic hardware on north exit doors. Remove manual flush bolts and 4x4 brackets. Provide sticker at both main exits see note #5. Provide exit discharge lighting per sheet A1.0. Provide occupant load sign "261"
BLD05-00634 FIRE-Final Inspection7/28/20057/28/20057/28/2005 1:25:40 PMPPART
tom hays ###-#### A temporary occupancy was given until the fire alarm and fire sprinkler permit have been finaled
FIR05-00358 INSP-Final Inspection7/28/20057/28/20057/28/2005 1:23:20 PMAPART
A temporary occupancy was given until the fire alarm plans with plan modifications have been approved.
BLD04-02272 FIRE-Final Inspection7/27/20057/28/20057/28/2005 12:18:58 PMAPART
A temporary occupancy was given wit sam rogers permission until the three duct smoke detectors have been placed correctly and tested
FIR04-00737 INSP-Sprinkler Rough-in/Hydro7/27/20057/28/20057/28/2005 12:16:09 PMAPASS
Above ground hydro test passed.
BLD04-02231 FIRE-Final Inspection7/27/20057/28/20057/28/2005 7:57:50 AMAPASS
Fire life safety finaled