Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02780 Rough-In Permanent Service7/28/20067/28/20067/28/2006 3:54:30 PMPCANC
shelly - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see p/s and ri
ELE06-02780 Electrical Rough-In7/28/20067/28/20067/28/2006 3:50:39 PMPFAIL
called contr, left corr notice, nec 210.52(A)(2) recpt shall be installed in 2' wall space (rear entry), 300.4(A) edge of holes shall be 1 1/4" from edge of framing member, 414.20 in walls of combustible material, boxes shall be flush with finished surface BCC all make-up shall be done-kitchen
ELE06-02780 Permanent Service7/28/20067/28/20067/28/2006 3:42:02 PMPPASS
shelly - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s u/g n ok
ELE06-02788 Rough-In Permanent Service7/28/20067/28/20067/28/2006 3:40:17 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Dan Rohl see p/s and ri
ELE06-02788 Electrical Rough-In7/28/20067/28/20067/28/2006 3:39:39 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called contr, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 314.4 all metal boxes shall be grounded per art. 250, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 210.52(A)(1) recpts shall be installed in wall space such that no point is over 6' from a recpt, 110.3(A) jetted tub shall be approved for installation by listing or labelling, BCC all make-up shall be done- range, microwave, recpts by fireplace, kitchen closet
ELE06-02788 Permanent Service7/28/20067/28/20067/28/2006 3:32:54 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dan Rohl p/s u/g n ok
ELE06-02004 Final7/27/20067/28/20067/28/2006 1:57:03 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Zane Robertson called contr, left corr notice, BCC no ceiling tiles shall be installed prior to ceiling inspection, rest ok
ELE06-02007 Final7/28/20067/28/20067/28/2006 1:36:53 PMPPASS
otis - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-01702 Electrical Rough-In7/28/20067/28/20067/28/2006 1:17:26 PMPPASS
MIKE nOTE: GAZEBO; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to add 1 room for gazebo, ric ok, no green sticker
ELE06-02780 Electrical Rough-In7/27/20067/28/20067/28/2006 11:54:57 AMACANC
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, no address
ELE06-01985 Final7/27/20067/28/20067/28/2006 10:53:10 AMAFAIL
Scheduled by a contractor via Hello! on 7/27/2006 at 2:19:21 PM. Contact: ###-####. called, left message, left correction notice, fee due, nec 110.12(C) there shall be no broken parts(garage recpt faceplate) 410.8(D) upper closet fixture shall not be closer than 12" to point of storage over shelves, 410.12 fixture shall be installed to box in bath,406.4 recpt in front shall be mounted in box w/ wp cover
ELE06-02130 Final7/27/20067/28/20067/28/2006 10:46:06 AMAPASS
Scheduled by a contractor via Hello! on 7/27/2006 at 2:19:55 PM. Contact: ###-####. ok to final
ELE05-03916 Final7/27/20067/28/20067/28/2006 9:56:04 AMAPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL corr made, ok to final
ELE06-00179 Final7/27/20067/28/20067/28/2006 9:55:23 AMAPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL corr made, ok to final
ELE06-02754 Conference7/27/20067/28/20067/28/2006 9:10:41 AMADONE
tom Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 336 did
ELE06-02742 Electrical Rough-In7/27/20067/28/20067/28/2006 9:10:12 AMADONE
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy 336 did
ELE06-00113 Electrical Rough-In7/27/20067/28/20067/28/2006 8:52:27 AMAPART
contact: Greg Pack ceiling inspection 6th floor; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover borders in halls fl 6,7 anop