Inspections for the day of: Friday, July 28, 2006.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00500 FIR-Aging Inspection7/28/20067/28/20068/2/2006 1:38:51 PM DEFR
FIR06-00481 INSP-Final Inspection7/27/20067/28/20067/30/2006 10:32:09 PMPDEFR
No time available for this inspection today, to be rescheduled.
BLD06-00239 FIRE-Final Inspection7/28/20067/28/20067/30/2006 10:31:28 PMPDEFR
cory; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley No time available for this inspection today, to be rescheduled.
FIR06-00451 INSP-Sprinkler Rough-in7/28/20067/28/20067/30/2006 10:30:46 PMPDEFR
###-#### colin No time available for this inspection, to be rescheduled.
FIR06-00510 INSP-Sprinkler Rough-in/Hydro7/27/20067/28/20067/28/2006 4:37:12 PMAPART
UG hydrostatic test is acceptable.
FIR06-00476 INSP-Sprinkler Rough-in7/27/20067/28/20067/28/2006 4:21:28 PMAFAIL
Relocate one head at basement closet, one drop is overspaced at basement room, tenting is not adequate at three riser locations on swing joints and is missing above branch lines in the family room, discussed freeze protection for lines in the garage area.
BLD05-02412 FIRE-Final Inspection7/28/20067/28/20067/28/2006 3:19:55 PMPPASS
Life safety inspection passed.
BLD05-02410 FIRE-Final Inspection7/28/20067/28/20067/28/2006 3:19:26 PMPPASS
Life safety is acceptable, inspection passed.
BLD05-02411 FIRE-Final Inspection7/28/20067/28/20067/28/2006 3:18:06 PMPPASS
Life safety is satisfactory, inspection passed.
FIR06-00487 INSP-Sprinkler Rough-in7/27/20067/28/20067/28/2006 2:59:22 PMPPART
OH rough-in inspection for concealed upright heads at entrance to the bargain cave and EC11 head drops in ceiling tile at retail area as marked on plans are okay to cover. Inspection for heads in racks below walkway in the storage area are acceptable except as marked on plan including missing coverage at one area requiring an additional head, heads at two locations are blocked, one head needs to be replaced due to missing liquid in glass bulb, need to install head guards at all locations where uprights are subject to mechanical damage in the racking system.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro7/27/20067/28/20067/28/2006 1:22:00 PMPFAIL
Inspection for cover at the drop ceiling areas in the lobby first floor failed due to architectural changes not shown on sprinkler plans which affect layout, significant field changes in head location from approved plans, lacking proper coverage at some locations. Submit approved plans reflecting changes and revised sprinkler head locaitons prior to next inspection for cover at this area.
BLD06-00276 FIRE-Final Inspection7/28/20067/28/20067/28/2006 1:00:19 PMPFAIL
Need to provide current inspection tags and lower the mounting height of the two provided fire extinguishers, exit signs and emergency lights failed to function on battery backup, door hardware at the west front door, back door, and small office do not meet code requirements, pocket door at the break room will need approved hardware or be removed. See fire code review notes for general requirements.
FIR06-00530 INSP-Sprinkler Rough-in/Hydro7/27/20067/28/20067/28/2006 12:55:05 PMPPART
OH rough-in is acceptable for cover at the hard lid and drop ceiling areas.
FIR06-00321 INSP-Sprinkler Rough-in/Hydro7/27/20067/28/20067/28/2006 11:54:40 AMANR
Items on previous correction notice are not yet completed for reinspection per phone conversation with contractor.
BLD04-02856 FIRE-Final Inspection7/27/20067/28/20067/28/2006 10:47:34 AMAFAIL
The project related fire alarm permit must be inspected, approved and finaled prior to BLD life safety final, need to provide building street address numbers per review note #7, repair exit signs at two locations, install knox box. Noted three defficiencies to GC related to FA while on site.
FIR06-00213 INSP-Supply line flush7/27/20067/28/20067/28/2006 10:03:57 AMAPART
UG fire supply line flush performed satisfactory.
BLD06-01453 FIRE-Final Inspection7/27/20067/28/20067/28/2006 9:28:51 AMAPASS
c/n items are complete, life safety field inspection passed.
BLD05-01304 FIRE-Final Inspection7/27/20067/28/20067/28/2006 9:25:43 AMAPASS
Shell and core life safety passed inspection.