Inspections for the day of: Monday, July 28, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00427 INSP-Final Inspection7/23/20087/28/20087/28/2008 5:34:31 PMPFAIL
Notification appliances as installed at two locations do not meet the intended application-wall mounted av's attatched to the ceiling.
FIR07-00606 INSP-Sprinkler Rough-in7/25/20087/28/20087/28/2008 5:04:35 PMAFAIL
Second reinspection for areas E, F, J and I, failed due to missed or incorrect repairs including exceeded min. spacing for heads at two locations, pendent head at a storage closet still does not meet obstruction table per NFPA 13 8.6.5.1.2, mixed heads at second floor classroom 103. Some items verified for correction initialed okay on plans with today's date.
BLD07-00421 FIRE-Final Inspection7/25/20087/28/20087/28/2008 3:11:47 PMPFAIL
Provide approved hardware at the main entry/exit door, the required fire extinguisher installed while on site, also need approved hardware at the new ADA restroom door, see circled items on stamped plan set under general notes for details of basic life safety requirements.
BLD08-00493 FIRE-Final Inspection7/25/20087/28/20087/28/2008 2:22:22 PMAPASS
Deficiencies listed and annotated on plans per last inspection have been corrected, fire life safety passed.
BLD08-01459 FIRE-Conference7/28/20087/28/20087/28/2008 2:01:06 PMPDONE
Site review of life safety issues including backup power source for the exit signs, door hardware, fire extinguishers, and project related fire sprinkler permit.
BLD08-01265 FIRE-Final Inspection7/28/20087/28/20087/28/2008 1:53:07 PMPPASS
Life safety finaled.
FIR08-00472 INSP-Final Inspection7/25/20087/28/20087/28/2008 11:29:00 AMAPASS
Fire alarm system modifications tested acceptable, noted changed EOL location, DH operated correctly however the doors do not close due to improper adjustments and floor covering-notified contractor to repair prior to final fire life safety inspection. Fire alarm permit finaled.
BLD08-01265 FIRE-Final Inspection7/28/20087/28/20087/28/2008 11:24:10 AMAPASS
The remainder of C/N items verified for compliance, final life safety passed.
BLD08-00958 FIRE-Final Inspection7/25/20087/28/20087/28/2008 11:17:26 AMAPASS
Fire life safety inspection completed satisfactory.
BLD08-00957 FIRE-Final Inspection7/25/20087/28/20087/28/2008 11:15:34 AMAPASS
Corrections are complete, fire life safety passed.