Inspections for the day of: Tuesday, July 28, 2009.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00068 ELE-Aging Inspection7/28/20097/28/20097/31/2009 4:00:20 PM DONE
no activity, waiting for contractor to set up meeting for inspection
ELE09-00717 ELE-Aging Inspection7/28/20097/28/20097/31/2009 3:58:24 PM DONE
no activity, waiting for contractor
ELE09-00176 ELE-Aging Inspection7/28/20097/28/20097/31/2009 3:57:06 PM DONE
no activity, waiting for contractor
ESC09-00389 General Inspection7/28/20097/28/20097/28/2009 4:28:19 PMPPART
called 315 and 360, assigned inspection to 360
ESC09-00398 General Inspection7/28/20097/28/20097/28/2009 4:27:25 PMPPART
called 315 and 360, assigned inspection request to 360
ELE08-02536 Electrical Rough-In7/28/20097/28/20097/28/2009 4:19:27 PMPPART
Requesting a partial ceiling inspection to cover.
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ceilings ok to cover music room and south c wing except dental area anop
ESC08-00457 General Inspection7/28/20097/28/20097/28/2009 3:42:55 PMPPASS
looked ok
ESC09-00332 General Inspection7/28/20097/28/20097/28/2009 3:19:49 PMPPASS
looked ok
ESC09-00433 General Inspection7/28/20097/28/20097/28/2009 3:00:30 PMPPASS
looked ok
ELE09-01354 Electrical Rough-In7/28/20097/28/20097/28/2009 1:55:04 PMPPASS
lars Phone #: ###-#### corrections made, ric 2 east units only ok
ELE09-01264 Final7/28/20097/28/20097/28/2009 12:44:35 PMPPASS
wire new A/C unit everthing on outside, any questions please call Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose called contractor, ok to final, no esc this project
ELE09-01264 Electrical Rough-In7/28/20097/28/20097/28/2009 12:33:31 PMPPASS
wire new A/C unit everthing on outside, any questions please call Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose called, ric ok, no esc this project
ELE09-01362 Final7/27/20097/28/20097/28/2009 10:19:12 AMAPASS
ext 1-chris-please call at least 30 mins prior to inspection Phone #: ###-#### ok to final, no esc this project
ELE09-01362 Electrical Rough-In7/28/20097/28/20097/28/2009 10:16:14 AMAPASS
ext 1-chris-please call at least 30 mins prior to inspection Phone #: ###-#### u/g ok to cover pole to house, no esc this project
ELE09-01349 Electrical Rough-In7/27/20097/28/20097/28/2009 9:46:07 AMAPASS
finishing the basement Phone #: ###-#### Internet Inspection Request from: Stephen Kren ric ok, no esc this project
ELE09-01365 Electrical Rough-In7/27/20097/28/20097/28/2009 8:54:23 AMAPASS
Reguest electrical rough-in on addition. Phone #: ###-#### Internet Inspection Request from: Tim Lawrence called, ric ok
ELE09-01354 Electrical Rough-In7/27/20097/28/20097/28/2009 8:12:49 AMAFAIL
Lars Phone #: ###-#### called, left correction notice, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members or use steel plates for protection, 210.52(A)(1) receptacles shall be spaced such that no point along wall line is over 6' from an outlet, 250.24(A) grounded conductor shall be connected to grounding electrode at service only, 348.30 fmc shall be securely fastened within 12" of box, BCC shall provide boxes for nm termination points, no violations shall be retained
ELE09-01349 Electrical Rough-In7/27/20097/28/20097/27/2009 3:19:06 PMPCANC
cust is finishing the basement Phone #: ###-#### Internet Inspection Request from: Stephen Kren Inspection cancelled from web by: Stephen Kren