Inspections for the day of: Thursday, July 28, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00267 INSP-Conference7/28/20117/28/20117/28/2011 4:19:54 PMPDONE
Regarding project inspection schedule.
FIR11-00285 INSP-Sprinkler Rough-in7/28/20117/28/20117/28/2011 4:18:47 PMPNR
BLD11-01002 FIRE-Final Inspection7/28/20117/28/20117/28/2011 4:17:17 PMPFAIL
Missing doors and hardware at several locations, new office walls are not yet finished, need to post fire extinguisher per plan, remove manual thumbturn at the main entry/exit, provide approved hardware at the second exit.
BLD11-01002 FIRE-Sprinkler Rough-in7/28/20117/28/20117/28/2011 4:14:49 PMPPART
Okay to cover fire sprinkler modifications at the drop ceilings.
BLD11-01659 FIRE-Final Inspection7/28/20117/28/20117/28/2011 4:13:43 PMPFAIL
Correction notice items include; post address numbers, repair one exit sign, post fire extinguishers as discussed, fire sprinklers are obstructed by overhead doors when in the extended postion. See item numbers 1,4 and 5 on the list of general requirements in the permit documents. Fire sprinkler work shall require an FIR permit.
FIR10-00540 INSP-Sprinkler Rough-in/Hydro7/28/20117/28/20117/28/2011 1:04:40 PMAPART
Hydrostatic testing finished.
FIR11-00356 INSP-Final Inspection7/27/20117/28/20117/28/2011 1:03:36 PMAPASS
Fire sprinkler permit work approved for final status.
BLD11-01110 FIRE-Final Inspection7/27/20117/28/20117/28/2011 1:02:21 PMAPASS
Scope of permit work passed life safety inspection. Fire extinguishers posted as discussed.