ELE12-02733
| ELE-Aging Inspection | 7/28/2014 | 7/28/2014 | 8/4/2014 9:23:12 AM | | DONE |
|
|
Drove by
|
ELE12-00661
| ELE-Aging Inspection | 7/28/2014 | 7/28/2014 | 7/29/2014 11:28:28 AM | | DONE |
|
|
Wait on owner
|
ELE14-01283
| Final | 7/28/2014 | 7/28/2014 | 7/28/2014 2:59:21 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Steve Craig No card posted. Final ok
|
ELE14-00775
| Final | 7/25/2014 | 7/28/2014 | 7/28/2014 2:13:41 PM | P | FAIL |
|
|
Toby. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 110.3- All 120 volt receptical outlets off ISO panels show open ground.
|
ELE14-01513
| Final | 7/28/2014 | 7/28/2014 | 7/28/2014 12:53:33 PM | P | FAIL |
|
|
lock box code 2267 Phone #: ###-#### >> Inspection requested via web by John Edwards 210.8(B)(2)- Other to dwelling units all 120 volt 15 and 20 amp recpticals located in kitchen area shall have GFCI protection. Freezer outlets and unable to verify other due to not working.
|
ELE13-03141
| Final | 7/25/2014 | 7/28/2014 | 7/28/2014 12:48:44 PM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender 314.20- Boxes set back in tile more than 1/4" chall have spark rings. 408.4 house panel, panel schedule shall be complete. 110.3- open neutral and hot neutral reversed in 3 locations. 422.30- Where water heater are not with in sight of panels provide lock out for disconnecting means.
|
ELE13-03142
| Final | 7/25/2014 | 7/28/2014 | 7/28/2014 12:48:19 PM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender. 314.20- Boxes set back in tile more than 1/4" shall have spark ringss. 406.11- All 120 volt 15 and 20 amp recepticals installed in residence shall be tamper resistant type. 408.4- House panel- panel schedule shall be completed. 422.30- where water heaters sre not with in sight of panels provide lockout for disconnecting means.
|
ELE13-00015
| Final | 7/27/2014 | 7/28/2014 | 7/28/2014 11:32:58 AM | A | PASS |
|
|
call for key location please thanks rex Phone #: ###-#### >> Inspection requested via web by Rex Boyles Final ok
|
ELE13-03157
| Final | 7/25/2014 | 7/28/2014 | 7/28/2014 8:34:47 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender Final ok
|