Inspections for the day of: Monday, July 28, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02733 ELE-Aging Inspection7/28/20147/28/20148/4/2014 9:23:12 AM DONE
Drove by
ELE12-00661 ELE-Aging Inspection7/28/20147/28/20147/29/2014 11:28:28 AM DONE
Wait on owner
ELE14-01283 Final7/28/20147/28/20147/28/2014 2:59:21 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Steve Craig No card posted. Final ok
ELE14-00775 Final7/25/20147/28/20147/28/2014 2:13:41 PMPFAIL
Toby. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 110.3- All 120 volt receptical outlets off ISO panels show open ground.
ELE14-01513 Final7/28/20147/28/20147/28/2014 12:53:33 PMPFAIL
lock box code 2267 Phone #: ###-#### >> Inspection requested via web by John Edwards 210.8(B)(2)- Other to dwelling units all 120 volt 15 and 20 amp recpticals located in kitchen area shall have GFCI protection. Freezer outlets and unable to verify other due to not working.
ELE13-03141 Final7/25/20147/28/20147/28/2014 12:48:44 PMAFAIL
Phone #: ###-#### >> Inspection requested via web by kendall bender
314.20- Boxes set back in tile more than 1/4" chall have spark rings.
408.4 house panel, panel schedule shall be complete.
110.3- open neutral and hot neutral reversed in 3 locations.
422.30- Where water heater are not with in sight of panels provide lock out for disconnecting means.
ELE13-03142 Final7/25/20147/28/20147/28/2014 12:48:19 PMAFAIL
Phone #: ###-#### >> Inspection requested via web by kendall bender.
314.20- Boxes set back in tile more than 1/4" shall have spark ringss.
406.11- All 120 volt 15 and 20 amp recepticals installed in residence shall be tamper resistant type.
408.4- House panel- panel schedule shall be completed.
422.30- where water heaters sre not with in sight of panels provide lockout for disconnecting means.
ELE13-00015 Final7/27/20147/28/20147/28/2014 11:32:58 AMAPASS
call for key location please thanks rex Phone #: ###-#### >> Inspection requested via web by Rex Boyles Final ok
ELE13-03157 Final7/25/20147/28/20147/28/2014 8:34:47 AMAPASS
Phone #: ###-#### >> Inspection requested via web by kendall bender Final ok