Inspections for the day of: Monday, July 28, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02104 ELE-Aging Inspection7/28/20147/28/20147/31/2014 6:49:18 AM DONE
still under construction
ELE12-02665 ELE-Aging Inspection7/28/20147/28/20147/28/2014 1:24:52 PM DONE
Did contact electrical contractor receptionist, discussed required final inspection.
ELE13-02849 Electrical Rough-In7/28/20147/28/20147/28/2014 1:18:14 PMPPASS
ceiling cover inspection - contact is Alan Krishnek Phone #: ###-#### >> Inspection requested via web by Scott Campbell rough-in ok cover pac-u ceiling grid
ELE14-02041 Temporary Service7/28/20147/28/20147/28/2014 12:55:06 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov t/s u/g n ok
ELE14-02043 Temporary Service7/28/20147/28/20147/28/2014 12:52:02 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov t/s u/g n ok
ELE14-02042 Temporary Service7/28/20147/28/20147/28/2014 12:49:09 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel t/s u/g n ok
ELE14-02044 Temporary Service7/28/20147/28/20147/28/2014 12:48:15 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov t/s u/g n ok
ELE14-02035 Permanent Service7/25/20147/28/20147/28/2014 11:07:31 AMANH
Unit # 92 * call- ###-#### for access *
Idaho Power Requested Inspection
** Please Call- ###-#### for access ** Phone #: ###-#### >> Inspection requested via web by Dan Hobdey No access contact person requires 30 min. notice.
ELE14-01833 Electrical Rough-In7/25/20147/28/20147/28/2014 10:44:26 AMAFAIL
Wayne-Hearing Booth Phone #: ###-#### NEC 320.12(1) Install where subject to physical damage. MC installed running length wise inside 2x4 steel studs.
ELE14-02040 Final7/27/20147/28/20147/28/2014 10:25:18 AMAPASS
wire ac Phone #: ###-#### >> Inspection requested via web by PAT MILLER job complete, final ok
ELE14-02040 Electrical Rough-In7/27/20147/28/20147/28/2014 10:23:36 AMAPASS
wire ac Phone #: ###-#### >> Inspection requested via web by PAT MILLER rough-in ok
ELE14-02029 Permanent Service7/25/20147/28/20147/28/2014 9:43:15 AMAFAIL
The access code is 4780, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren NEC 110.26(3)(F)(1)(a) Dedicated electrical space No piping below panel NEC 210.4(B) Common trip breakers for multiwire branch circuits NEC 240.24(A) Panel height NEC 250 250.56 upgrade service grounding 334.30 Securing NM cable within 12 in. of panel nail plates, KO plugs, Identify current carrying conductors
ELE13-02849 Electrical Rough-In7/25/20147/28/20147/28/2014 8:41:36 AMANR
Contact is Alan Krishnek - ceiling inspection Phone #: ###-#### >> Inspection requested via web by Scott Campbell not ready