Inspections for the day of: Tuesday, July 28, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01434 ELE-Aging Inspection7/28/20157/28/20157/30/2015 10:20:50 AM CANC
too busy
ELE13-00910 ELE-Aging Inspection7/28/20157/28/20157/30/2015 10:20:30 AM CANC
too busy
ELE12-02104 ELE-Aging Inspection7/28/20157/28/20157/28/2015 2:33:18 PM DONE
Still under construction
ELE15-02069 Final7/28/20157/28/20157/28/2015 2:26:01 PMPNR
Final at Starbucks remodel. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Contractor called and said he would not be ready by PM. Will reschedule
ELE15-01154 Permanent Service7/27/20157/28/20157/28/2015 2:09:17 PMPPASS
Ryan Phone #: ###-#### p/s u/g rec ok
ELE15-01913 Permanent Service7/27/20157/28/20157/28/2015 1:27:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Bryan Atkins p/s u/g n ok
ELE15-02331 Rough-In Permanent Service7/28/20157/28/20157/28/2015 12:20:43 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov This address is wrong house sits on 11292 Race st. Contractor will recall when corrected.
ELE15-02270 Permanent Service7/27/20157/28/20157/28/2015 11:26:07 AMAPASS
JR Phone #: ###-#### p/s u/g n ok
ELE15-01301 Permanent Service7/27/20157/28/20157/28/2015 10:59:59 AMACANC
Dan Hommell Phone #: ###-#### Inspection requested via web by Kerri Hamilton Needed rough in inspection
ELE15-01301 Electrical Rough-In7/28/20157/28/20157/28/2015 10:59:30 AMPPASS
Dan Hommell Phone #: ###-#### Inspection requested via web by Kerri Hamilton Bi-plane ceiling and UPS power rough in ok cover
ELE15-02104 Final7/28/20157/28/20157/28/2015 10:16:07 AMPPASS
Rough in inspection if done early enough Phone #: ###-#### Inspection requested via web by George Stanton Final ok
ELE15-01551 Final7/27/20157/28/20157/28/2015 10:01:25 AMAPASS
John Phone #: ###-#### Final ok
ELE15-01551 Electrical Rough-In7/28/20157/28/20157/28/2015 10:01:10 AMPPASS
John Phone #: ###-#### Hot tub rough in ok cover
ELE15-02305 Rough-In Permanent Service7/27/20157/28/20157/28/2015 9:26:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
ELE15-02104 Electrical Rough-In7/28/20157/28/20157/28/2015 8:37:28 AMPPASS
Rough in inspection if done early enough Phone #: ###-#### Inspection requested via web by George Stanton UL listing and proper bonding equipment Confirmed. Rough in ok cover
ELE15-01517 Electrical Rough-In7/27/20157/28/20157/27/2015 3:06:42 PMAFAIL
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams 210.62- Show window receptacle outlets shall be installed. Existing sign cord shall not be above grid as per 400.8
300.11- Exit sign boxes shall be supported independant of grid.
330.40- Large box above west wall connector installation not complete.