Inspections for the day of: Thursday, July 28, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00751 INSP-Conference7/27/20167/28/20167/28/2016 7:33:38 PMADONE
Fire alarm conference complete, tested smoke detectors associated with shell and core on levels 1 through 9, tested audio visual devices associated with shell and core on floors 1 through 9, tested loss of battery power trouble at main panel.
BLD15-03767 FIRE-Final Inspection7/28/20167/28/20167/28/2016 3:28:22 PMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00069 INSP-Final Inspection7/28/20167/28/20167/28/2016 3:25:46 PMPPASS
Final fire alarm inspection passed/complete
FIR16-00449 INSP-Sprinkler Rough-in7/26/20167/28/20167/28/2016 3:24:50 PMPPASS
Rough to cover inspection for underground supply complete, underground supply approved for cover.
FIR16-00321 INSP-Final Inspection7/28/20167/28/20167/28/2016 3:23:52 PMPFAIL
Tank actuator did not operate when clean agent fire panel was in alarm. Contractor will troubleshoot and reschedule inspection request when issue is resolved.
FIR16-00114 INSP-Final Inspection7/27/20167/28/20167/28/2016 3:20:17 PMPPASS
Final fire sprinkler inspection for level 3 complete.
FIR16-00200 INSP-Sprinkler Rough-in7/27/20167/28/20167/28/2016 3:18:40 PMAPART
24 hour air test started at 1:15pm @ 42psi
FIR16-00344 INSP-Sprinkler Rough-in7/27/20167/28/20167/28/2016 11:59:06 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping located above ceiling grid area's complete, overhead fire sprinkler piping located above ceiling grid area's from middle of tenant space north approved for cover.
FIR16-00305 INSP-Sprinkler Rough-in7/27/20167/28/20167/28/2016 11:30:49 AMAPART
Partial rough to cover inspection for overhead fire sprinkler piping located on level 3 complete, notated the city approved drawings with pink highlighter/red ink area's approved for cover.
BLD16-01567 FIRE-Final Inspection7/27/20167/28/20167/28/2016 10:57:53 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Noted that the general contractor was informed about the thumbturn deadbolts need to be changed, allowed one double keyed deadbolt and single action paddle type door hardware on other exterior door. Final life fire safety inspection passed/complete.
FIR15-00808 INSP-Sprinkler Rough-in7/27/20167/28/20167/28/2016 10:36:52 AMAPASS
Tenting inspection complete for level 3, all overhead fire sprinkler piping located in the attic space of level 3 approved for cover.
BLD16-01910 FIRE-Conference7/27/20167/28/20167/28/2016 10:17:41 AMADONE
Fire conference complete, tenant will need to contact a licensed contractor to perform a site survey for relocation/addition of exit signs and obstructed audio visual devices on the fire alarm system that is now blocked by the newly installed racks. Any work performed on the fire alarm system will require an FIR permit for work to be completed.
FIR16-00129 INSP-Final Inspection7/28/20167/28/20167/28/2016 9:43:37 AMPPASS
Final fire sprinkler inspection passed/complete
FIR16-00155 INSP-Sprinkler Rough-in7/27/20167/28/20167/28/2016 9:36:52 AMPPART
Rough to cover inspection complete for 4th floor south bathrooms, south 4th floor bathrooms approved for cover.
FIR15-00795 INSP-Final Inspection7/27/20167/28/20167/28/2016 8:58:14 AMPCANC
Please call Jake when you are headed out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello