Inspections for the day of: Friday, July 28, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01965 Electrical Rough-In7/28/20177/28/20177/28/2017 1:35:27 PMPPASS
Marco-radiant floors Phone #: ###-####-please call when your on your way
Listing and class A GFCI protection at thermostat confirmed. Rough in ok cover
ELE17-01220 Final7/28/20177/28/20177/28/2017 1:11:12 PMPFAIL
Phone #: ###-#### Inspection requested via web by Emmet Bushman
250.32- Building fed with feeders or branch circuits shall have a grounding electrode system installed.
Unable to gain access to house or garage. house has sign stating wet floors no access until 7-29-17 no acceptions and garage has wet concrete at all entrances.
ELE17-01472 Final7/27/20177/28/20177/28/2017 11:53:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
ELE17-00500 Final7/28/20177/28/20177/28/2017 11:52:55 AMPPASS
Underground Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
ELE17-01473 Final7/27/20177/28/20177/28/2017 11:52:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
Final ok
ELE17-02439 Rough-In Permanent Service7/27/20177/28/20177/28/2017 11:26:18 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ben Archibald
BCC 4 05 23- It shall be unlawful to conceal electrical wiring prior to inspection. Soffits covered prior with several cans, paddle fan, receptacle. Front and both back patios.
300.4- Nail plates required pantry and under stairs.
334.15(B)- NM cable shall not be install where subject to damage. touching top of fireplace flue.
Fee due on single family dwelling under 2500 sq. ft. $135.00- $55.00= $80.00.
Need permit for pool
OK foam seal only
ELE17-02425 Electrical Rough-In7/27/20177/28/20177/28/2017 10:01:04 AMAPASS
Under ground and wall inspection Phone #: ###-#### Inspection requested via web by Ben Archibald
Underground to be 30"+ once back fill is in. Underground and walls rough in ok cover
ELE17-02413 Electrical Rough-In7/27/20177/28/20177/28/2017 9:06:38 AMAPASS
Please call Norm 30 minutes prior to going out to the home, so that he has enough time to get over there the house. Phone #: ###-#### Inspection requested via web by Eric Schroeder
Wiring on surface of pocket doors to have batting on each side of wiring for drywall. Down bed wall with pocket doors only rough in ok cover
ELE17-02360 Electrical Rough-In7/26/20177/28/20177/28/2017 8:45:15 AMAPASS
Underground/underslab inspection. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery
2 to n.e. corner, 2 to s.w.corner, several interior and feeders underground and slab rough in ok cover