ELE16-01965
| Electrical Rough-In | 7/28/2017 | 7/28/2017 | 7/28/2017 1:35:27 PM | P | PASS |
|
|
Marco-radiant floors Phone #: ###-####-please call when your on your way Listing and class A GFCI protection at thermostat confirmed. Rough in ok cover
|
ELE17-01220
| Final | 7/28/2017 | 7/28/2017 | 7/28/2017 1:11:12 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman 250.32- Building fed with feeders or branch circuits shall have a grounding electrode system installed. Unable to gain access to house or garage. house has sign stating wet floors no access until 7-29-17 no acceptions and garage has wet concrete at all entrances.
|
ELE17-01472
| Final | 7/27/2017 | 7/28/2017 | 7/28/2017 11:53:46 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
|
ELE17-00500
| Final | 7/28/2017 | 7/28/2017 | 7/28/2017 11:52:55 AM | P | PASS |
|
|
Underground Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
|
ELE17-01473
| Final | 7/27/2017 | 7/28/2017 | 7/28/2017 11:52:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
|
ELE17-02439
| Rough-In Permanent Service | 7/27/2017 | 7/28/2017 | 7/28/2017 11:26:18 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald BCC 4 05 23- It shall be unlawful to conceal electrical wiring prior to inspection. Soffits covered prior with several cans, paddle fan, receptacle. Front and both back patios. 300.4- Nail plates required pantry and under stairs. 334.15(B)- NM cable shall not be install where subject to damage. touching top of fireplace flue. Fee due on single family dwelling under 2500 sq. ft. $135.00- $55.00= $80.00. Need permit for pool OK foam seal only
|
ELE17-02425
| Electrical Rough-In | 7/27/2017 | 7/28/2017 | 7/28/2017 10:01:04 AM | A | PASS |
|
|
Under ground and wall inspection Phone #: ###-#### Inspection requested via web by Ben Archibald Underground to be 30"+ once back fill is in. Underground and walls rough in ok cover
|
ELE17-02413
| Electrical Rough-In | 7/27/2017 | 7/28/2017 | 7/28/2017 9:06:38 AM | A | PASS |
|
|
Please call Norm 30 minutes prior to going out to the home, so that he has enough time to get over there the house. Phone #: ###-#### Inspection requested via web by Eric Schroeder Wiring on surface of pocket doors to have batting on each side of wiring for drywall. Down bed wall with pocket doors only rough in ok cover
|
ELE17-02360
| Electrical Rough-In | 7/26/2017 | 7/28/2017 | 7/28/2017 8:45:15 AM | A | PASS |
|
|
Underground/underslab inspection. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery 2 to n.e. corner, 2 to s.w.corner, several interior and feeders underground and slab rough in ok cover
|