NAF17-00027
| INSP-Sprinkler Rough-in | 7/27/2017 | 7/28/2017 | 7/28/2017 4:20:11 PM | A | PASS |
|
|
Rough to cover inspection for area of work complete, approved for cover.
|
NAF17-00029
| INSP-Sprinkler Rough-in | 7/27/2017 | 7/28/2017 | 7/28/2017 4:19:35 PM | P | CANC |
|
|
Inspection request was for main entry canopy, this inspection request is cancelled
|
BLD17-01694
| FIRE-Conference | 7/28/2017 | 7/28/2017 | 7/28/2017 3:32:21 PM | P | DONE |
|
|
Fire conference complete
|
BLD17-00984
| FIRE-Final Inspection | 7/28/2017 | 7/28/2017 | 7/28/2017 2:29:09 PM | P | FAIL |
|
|
Fire extinguisher needs to be serviced, last tagged inspection was in 2010. All emergency exit/egress lighting in space needs to be serviced, exit lights/egress lighting did no illuminate when power was shut off.
|
BLD17-01710
| FIRE-Conference | 7/28/2017 | 7/28/2017 | 7/28/2017 1:59:22 PM | P | DONE |
|
|
Fire conference is complete, exit discharge emergency lighting needs to be installed on the designated exterior exits on the west side exit in the warehouse and southeast exit (main entry into the office area). Current address on building reads 2701B, permit has the address as 2707, address needs to be verified and the correct numbering needs to be installed. There is an open FIR permit associated with this building permit, FIR17-00392 permt needs to be inspected and passed before life fire safety can be completed. The fire alarm system will be monitored when complete, the building currently does not have a knox box, a knox box needs to be installed before final life fire safety inspection.
|
BLD17-01710
| FIRE-Final Inspection | 7/28/2017 | 7/28/2017 | 7/28/2017 1:52:32 PM | P | CANC |
|
|
Inspection request is for a life fire safety conference, this inspection request is cancelled.
|
FIR17-00135
| INSP-Final Inspection | 7/28/2017 | 7/28/2017 | 7/28/2017 12:05:13 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD17-01460
| FIRE-Final Inspection | 7/27/2017 | 7/28/2017 | 7/28/2017 9:07:04 AM | A | PASS |
|
|
No fire sprinklers, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection passed/complete.
|
BLD17-01171
| FIRE-Final Inspection | 7/27/2017 | 7/28/2017 | 7/28/2017 8:44:47 AM | A | CANC |
|
|
Life fire safety signature not required in permit details, notified point of contact Tom Phone #: ###-####, this request is cancelled.
|