FIR19-00522
| INSP-Final Inspection | 7/24/2020 | 7/28/2020 | 7/28/2020 10:27:53 AM | A | FAIL |
|
|
Smoke detectors located farther than 60 inches away from doors with mag holders, smoke detectors must comply with 17.7.5.6 of NFPA72. 2 areas have audio visual notification exceeding 15 feet from end of corridor. Notatyed tenat space where a 30cd should have been provided but device was set at 15. Inspection was stopped due too defeciencies.
Please call Mike 1 hr before arriving. Phone #: ###-#### Inspection requested via web by James Williams
|
FIR19-00779
| INSP-Final Inspection | 7/27/2020 | 7/28/2020 | 7/28/2020 8:50:14 AM | A | PASS |
|
|
Previously noted item has been corrected, final fire sprinkler inspection is complete.
Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|