BLD03-01845
| FIRE-Conference | 7/22/2004 | 7/29/2004 | 8/2/2004 12:00:00 AM | P | PART |
|
|
To see if alarm plans have been submitted //// Tlaked to Phil and he is awaiting word from building owner 8/2/2004 2:54:18 PM
|
BLD04-00850
| FIRE-Conference | 7/28/2004 | 7/29/2004 | 7/29/2004 12:00:00 AM | A | PART |
|
|
Gene -- please call first. thanks.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Met with Gene about combustible cavity under the new stairs will require sprinklers or make noncombustible 7/29/2004 10:36:31 AM
|
BLD03-03078
| FIRE-Final Inspection | 7/29/2004 | 7/29/2004 | 7/29/2004 12:00:00 AM | A | PASS |
|
|
Fire/life safety okay for final 7/29/2004 10:37:52 AM
|
FIR04-00422
| INSP-Sprinkler Rough-in | 7/29/2004 | 7/29/2004 | 7/29/2004 12:00:00 AM | P | PART |
|
|
Kerry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Installed as shown on plans however the Type I hood extinguishing system has been reduced to cover a small appliance at the north end of the hood leaving the rest of the area under the hood unsprinklered; heads are overspaced in the prep area from the Type I hood - maintain 130 sq ft 7/29/2004 3:03:03 PM
|
FIR04-00422
| INSP-Final Inspection | 7/29/2004 | 7/29/2004 | 7/29/2004 12:00:00 AM | P | FAIL |
|
|
Kerry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes See rough-in inspection notes 7/29/2004 3:03:29 PM
|
FIR04-00131
| INSP-Sprinkler Rough-in/Hydro | 7/29/2004 | 7/29/2004 | 7/29/2004 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Cliff Miller
|