Inspections for the day of: Friday, July 29, 2005.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00422 INSP-Sprinkler Rough-in7/29/20057/29/20057/29/2005 3:49:53 PMPPART
Overhead fire sprinkler rough-in is satisfactory. Final pending installation of escutcheons, SW verification below catwalk, spare heads in headbox, verify current annual inspection on system.
MIS05-00105 FIR-Final7/29/20057/29/20057/29/2005 3:16:38 PMPFAIL
Provide approved hardware at all exterior exit doors as discussed- no thumbturns, manual bolts or knobs allowed, provide fire extinguishers with current annual inspection tag and handles mounted no higher than 48" AFF, cover open electrical junction box, repair doors and remove hardware at west bay interior doors.
BLD04-02203 FIRE-Conference7/29/20057/29/20057/29/2005 12:00:00 AMADONE
On site discussion with Phil Doble in regards to sprinkler code issues related to obstructions in a restroom by a soffit and by rolling cabinets in a records room.
BLD04-01882 FIRE-Conference7/29/20057/29/20057/29/2005 12:00:00 AMPDONE
Spoke with Jonathan at ###-#### and informed him the FIR and BLD life safety portions of this project have been finaled. I also made him aware that the MEC, ACH, and PLM permits are still showing in the "issued" status.