Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00684 INSP-Sprinkler Rough-in/Hydro7/29/20057/29/20057/29/2005 3:37:54 PMPPASS
Swimming pool area piping ok to cover
FIR05-00448 INSP-Conference7/29/20057/29/20057/29/2005 2:46:07 PMPDONE
###-#### jeff. Upright heads on both sides of beams to remain.
BLD05-01566 FIRE-Final Inspection7/28/20057/29/20057/29/2005 2:36:13 PMAPART
A temporary occupancy was given with sam rogers permission. This is for the A3 area only. The exit discharge lighting for all exits and the B occupancy area still needs addressed. There appears to be adequate street lighting in lew of exit discharge temporarily. Per electrician the correct exit discharge will be installled by tonight.
BLD04-02894 FIRE-Final Inspection7/29/20057/29/20057/29/2005 1:45:44 PMPPASS
paul; Phone #: ###-#### Fire life safety finaled
BLD05-01417 FIRE-Final Inspection7/29/20057/29/20057/29/2005 1:14:45 PMPFAIL
kevin; Phone #: ###-#### Relocate the exit signs as shown on the approved plans and remove the latch part of the restroom doors so that opening will occure with a single motion
FIR05-00124 INSP-Sprinkler Rough-in/Hydro7/28/20057/29/20057/29/2005 12:23:05 PMPPASS
contact dave. finish 24 hr air.; Air test passed
FIR04-00737 INSP-Sprinkler Rough-in/Hydro7/28/20057/29/20057/29/2005 12:22:08 PMPPASS
contact dave. finish 24 hr air; air test passed
FIR05-00091 INSP-Final Inspection7/26/20057/29/20057/29/2005 10:55:57 AMAPASS
Fire sprinklers finaled. Underground flush passed.
BLD05-00783 FIRE-Final Inspection7/28/20057/29/20057/29/2005 10:09:53 AMAFAIL
ted; Phone #: ###-#### Provide additional exit sign/emergency light in basement as marked on plans. Provide annual inspection for the basement fire sprinkler system. Provide enclosure for the duct smoke detector located outside on the roof. Test both duct smoke detectors. Provide accessible door hardware throughout building as per building review notes.
FIR05-00423 INSP-Final Inspection7/28/20057/29/20057/29/2005 8:20:59 AMAFAIL
lynde; Phone #: ###-#### Waited at the job site for 30 minutes for access to tenant but no one showed up.
FIR05-00333 INSP-Final Inspection7/28/20057/29/20057/28/2005 1:24:58 PMAPART
A temporary occupancy was given until the existing piping in the bridge has been removed as per the scope of work.