FIR04-00684
| INSP-Sprinkler Rough-in/Hydro | 7/29/2005 | 7/29/2005 | 7/29/2005 3:37:54 PM | P | PASS |
|
|
Swimming pool area piping ok to cover
|
FIR05-00448
| INSP-Conference | 7/29/2005 | 7/29/2005 | 7/29/2005 2:46:07 PM | P | DONE |
|
|
###-#### jeff. Upright heads on both sides of beams to remain.
|
BLD05-01566
| FIRE-Final Inspection | 7/28/2005 | 7/29/2005 | 7/29/2005 2:36:13 PM | A | PART |
|
|
A temporary occupancy was given with sam rogers permission. This is for the A3 area only. The exit discharge lighting for all exits and the B occupancy area still needs addressed. There appears to be adequate street lighting in lew of exit discharge temporarily. Per electrician the correct exit discharge will be installled by tonight.
|
BLD04-02894
| FIRE-Final Inspection | 7/29/2005 | 7/29/2005 | 7/29/2005 1:45:44 PM | P | PASS |
|
|
paul; Phone #: ###-#### Fire life safety finaled
|
BLD05-01417
| FIRE-Final Inspection | 7/29/2005 | 7/29/2005 | 7/29/2005 1:14:45 PM | P | FAIL |
|
|
kevin; Phone #: ###-#### Relocate the exit signs as shown on the approved plans and remove the latch part of the restroom doors so that opening will occure with a single motion
|
FIR05-00124
| INSP-Sprinkler Rough-in/Hydro | 7/28/2005 | 7/29/2005 | 7/29/2005 12:23:05 PM | P | PASS |
|
|
contact dave. finish 24 hr air.; Air test passed
|
FIR04-00737
| INSP-Sprinkler Rough-in/Hydro | 7/28/2005 | 7/29/2005 | 7/29/2005 12:22:08 PM | P | PASS |
|
|
contact dave. finish 24 hr air; air test passed
|
FIR05-00091
| INSP-Final Inspection | 7/26/2005 | 7/29/2005 | 7/29/2005 10:55:57 AM | A | PASS |
|
|
Fire sprinklers finaled. Underground flush passed.
|
BLD05-00783
| FIRE-Final Inspection | 7/28/2005 | 7/29/2005 | 7/29/2005 10:09:53 AM | A | FAIL |
|
|
ted; Phone #: ###-#### Provide additional exit sign/emergency light in basement as marked on plans. Provide annual inspection for the basement fire sprinkler system. Provide enclosure for the duct smoke detector located outside on the roof. Test both duct smoke detectors. Provide accessible door hardware throughout building as per building review notes.
|
FIR05-00423
| INSP-Final Inspection | 7/28/2005 | 7/29/2005 | 7/29/2005 8:20:59 AM | A | FAIL |
|
|
lynde; Phone #: ###-#### Waited at the job site for 30 minutes for access to tenant but no one showed up.
|
FIR05-00333
| INSP-Final Inspection | 7/28/2005 | 7/29/2005 | 7/28/2005 1:24:58 PM | A | PART |
|
|
A temporary occupancy was given until the existing piping in the bridge has been removed as per the scope of work.
|