Inspections for the day of: Tuesday, July 29, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC08-00265 General Inspection7/29/20087/29/20087/29/2008 4:11:13 PMPPASS
looked ok
ESC08-00466 General Inspection7/29/20087/29/20087/29/2008 4:10:21 PMPPASS
looked ok
ESC05-00016 General Inspection7/29/20087/29/20087/29/2008 4:08:55 PMAPASS
looked ok
ESC08-00035 General Inspection7/29/20087/29/20087/29/2008 4:07:33 PMAPASS
looked ok
ELE08-02034 Permanent Service7/28/20087/29/20087/29/2008 4:06:47 PMPCANC
Scheduled by a contractor via Hello! on 7/28/2008 at 4:40:10 PM. Contact: ###-####.see final, no esc this project
ELE08-02034 Final7/29/20087/29/20087/29/2008 4:06:17 PMPPASS
Scheduled by a contractor via Hello! on 7/28/2008 at 4:40:10 PM. Contact: ###-####. ok to final, no esc this project
ELE08-02104 Permanent Service7/29/20087/29/20087/29/2008 3:41:16 PMPFAIL
Robert Phone #: ###-#### talked with owner, left correction notice, NEC 240.4 shall use overcurrent protection for rating of cord conductors i.e. 50a in service panel,408.4 shall provide circuit directory, 552.43(B) shall provide strain relief for cord to prevent strain to terminals in panel, 230.24(A) shall provide 8' clearance for service conductors over roof, 110.13 the panel shall be securely mounted (wall is loose), 110.14 all electrical connections shall be made, no esc this project
ELE08-01623 Electrical Rough-In7/28/20087/29/20087/29/2008 3:03:37 PMPPART
Inspect trench for cover for gate operators at main entrance on Maplegrove and north entrance on Susan Drive. Phone #: ###-#### Internet Inspection Request from: Alan Lusk met electrician, ok to cover north entrance u/g only. South entrance was done by electrician and given ok by 315 due to working thru Ada County. Will have some more u/g later. no esc this project
ELE08-01713 Permanent Service7/29/20087/29/20087/29/2008 2:14:47 PMPPASS
The service has been upgraded from 200amp to 400amp. Need an inspection for upgraded service. Please call cory @ ###-#### with any questions. Phone #: ###-#### Internet Inspection Request from: Alison Pennington p/s o/h rec ok, no esc this project
ELE08-02093 Permanent Service7/28/20087/29/20087/29/2008 1:24:05 PMPPASS
early afternoon please. ok for Id Power to reconnect. Jared''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s u/g rec ok,no esc this project
ELE08-02100 Rough-In Permanent Service7/28/20087/29/20087/29/2008 1:10:51 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ric ok, p/s u/g n ok
ELE08-01558 Final7/29/20087/29/20087/29/2008 12:17:23 PMPPASS
JEREMY nOTE: PLEASE CALL 1/2 HR PRIOR TO INSPECTION Phone #: ###-#### ok to final
ELE08-01990 Final7/28/20087/29/20087/29/2008 11:35:45 AMAPASS
Pat, This house should be open please call with any problems. Phone #: ###-#### Internet Inspection Request from: jason shifflett ok to final, no esc this project
ELE08-02098 Rough-In Permanent Service7/28/20087/29/20087/29/2008 10:21:01 AMAPASS
vanzandt Phone #: ###-#### ric ok house and garage, ok to cover u/g, p/s o/h n ok, no esc this project
ELE08-02095 Final7/28/20087/29/20087/29/2008 9:37:54 AMAPASS
Dallas Beus is electrician.
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok to final, no esc this project
ELE06-00034 Electrical Rough-In7/28/20087/29/20087/29/2008 8:50:58 AMAFAIL
ken Phone #: ###-#### met owner ,corrections 300.4(A)&(D) shall provide 1 1/4" for bored holes and nm cable from face of framing member, 300.14 shall provide 6" free conductor length in boxes, 110.12(C) there shall be no broken boxes, NOTE: ok to cover concrete encased electrode, owner found rebar to tie to
ELE08-01029 Electrical Rough-In7/28/20087/29/20087/29/2008 8:07:39 AMAFAIL
danny Phone #: ###-#### met electrician, left correction notice, BCC no violations shall be retained, no lv shall be on tiles or grid,NEC 725.8 class 1,2,3 cables shall be supported by building structure with straps, hangars, or similar fittings and installed so as to not damage the cable and also conform to article 300.4(D), 400.8(5) cord shall not be concealed by ceilings or above dropped ceilings