ESC08-00265
| General Inspection | 7/29/2008 | 7/29/2008 | 7/29/2008 4:11:13 PM | P | PASS |
|
|
looked ok
|
ESC08-00466
| General Inspection | 7/29/2008 | 7/29/2008 | 7/29/2008 4:10:21 PM | P | PASS |
|
|
looked ok
|
ESC05-00016
| General Inspection | 7/29/2008 | 7/29/2008 | 7/29/2008 4:08:55 PM | A | PASS |
|
|
looked ok
|
ESC08-00035
| General Inspection | 7/29/2008 | 7/29/2008 | 7/29/2008 4:07:33 PM | A | PASS |
|
|
looked ok
|
ELE08-02034
| Permanent Service | 7/28/2008 | 7/29/2008 | 7/29/2008 4:06:47 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 7/28/2008 at 4:40:10 PM. Contact: ###-####.see final, no esc this project
|
ELE08-02034
| Final | 7/29/2008 | 7/29/2008 | 7/29/2008 4:06:17 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/28/2008 at 4:40:10 PM. Contact: ###-####. ok to final, no esc this project
|
ELE08-02104
| Permanent Service | 7/29/2008 | 7/29/2008 | 7/29/2008 3:41:16 PM | P | FAIL |
|
|
Robert Phone #: ###-#### talked with owner, left correction notice, NEC 240.4 shall use overcurrent protection for rating of cord conductors i.e. 50a in service panel,408.4 shall provide circuit directory, 552.43(B) shall provide strain relief for cord to prevent strain to terminals in panel, 230.24(A) shall provide 8' clearance for service conductors over roof, 110.13 the panel shall be securely mounted (wall is loose), 110.14 all electrical connections shall be made, no esc this project
|
ELE08-01623
| Electrical Rough-In | 7/28/2008 | 7/29/2008 | 7/29/2008 3:03:37 PM | P | PART |
|
|
Inspect trench for cover for gate operators at main entrance on Maplegrove and north entrance on Susan Drive. Phone #: ###-#### Internet Inspection Request from: Alan Lusk met electrician, ok to cover north entrance u/g only. South entrance was done by electrician and given ok by 315 due to working thru Ada County. Will have some more u/g later. no esc this project
|
ELE08-01713
| Permanent Service | 7/29/2008 | 7/29/2008 | 7/29/2008 2:14:47 PM | P | PASS |
|
|
The service has been upgraded from 200amp to 400amp. Need an inspection for upgraded service. Please call cory @ ###-#### with any questions. Phone #: ###-#### Internet Inspection Request from: Alison Pennington p/s o/h rec ok, no esc this project
|
ELE08-02093
| Permanent Service | 7/28/2008 | 7/29/2008 | 7/29/2008 1:24:05 PM | P | PASS |
|
|
early afternoon please. ok for Id Power to reconnect. Jared''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s u/g rec ok,no esc this project
|
ELE08-02100
| Rough-In Permanent Service | 7/28/2008 | 7/29/2008 | 7/29/2008 1:10:51 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ric ok, p/s u/g n ok
|
ELE08-01558
| Final | 7/29/2008 | 7/29/2008 | 7/29/2008 12:17:23 PM | P | PASS |
|
|
JEREMY nOTE: PLEASE CALL 1/2 HR PRIOR TO INSPECTION Phone #: ###-#### ok to final
|
ELE08-01990
| Final | 7/28/2008 | 7/29/2008 | 7/29/2008 11:35:45 AM | A | PASS |
|
|
Pat, This house should be open please call with any problems. Phone #: ###-#### Internet Inspection Request from: jason shifflett ok to final, no esc this project
|
ELE08-02098
| Rough-In Permanent Service | 7/28/2008 | 7/29/2008 | 7/29/2008 10:21:01 AM | A | PASS |
|
|
vanzandt Phone #: ###-#### ric ok house and garage, ok to cover u/g, p/s o/h n ok, no esc this project
|
ELE08-02095
| Final | 7/28/2008 | 7/29/2008 | 7/29/2008 9:37:54 AM | A | PASS |
|
|
Dallas Beus is electrician. Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok to final, no esc this project
|
ELE06-00034
| Electrical Rough-In | 7/28/2008 | 7/29/2008 | 7/29/2008 8:50:58 AM | A | FAIL |
|
|
ken Phone #: ###-#### met owner ,corrections 300.4(A)&(D) shall provide 1 1/4" for bored holes and nm cable from face of framing member, 300.14 shall provide 6" free conductor length in boxes, 110.12(C) there shall be no broken boxes, NOTE: ok to cover concrete encased electrode, owner found rebar to tie to
|
ELE08-01029
| Electrical Rough-In | 7/28/2008 | 7/29/2008 | 7/29/2008 8:07:39 AM | A | FAIL |
|
|
danny Phone #: ###-#### met electrician, left correction notice, BCC no violations shall be retained, no lv shall be on tiles or grid,NEC 725.8 class 1,2,3 cables shall be supported by building structure with straps, hangars, or similar fittings and installed so as to not damage the cable and also conform to article 300.4(D), 400.8(5) cord shall not be concealed by ceilings or above dropped ceilings
|