FIR09-00164
| INSP-Conference | 7/29/2009 | 7/29/2009 | 7/29/2009 5:20:01 PM | P | DONE |
|
|
On site meeting with CM company, United Water, and Boise School district regarding backflow prevention device locations at the main fire riser.
|
FIR09-00260
| INSP-Sprinkler Rough-in | 7/29/2009 | 7/29/2009 | 7/29/2009 5:15:41 PM | P | PART |
|
|
Okay to cover hard lid ceilings at the mens and womens restrooms per red lines and initials on stamped plan set.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 7/24/2009 | 7/29/2009 | 7/29/2009 5:13:46 PM | A | PART |
|
|
Begin 24 hr. pneumatic testing for 8 preaction systems at the freezer area including rack and overhead systems-start time @ 4:00pm.
|
FIR09-00290
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 5:10:59 PM | A | FAIL |
|
|
Walkthrough completed for the dry goods warehouse and office areas, noted lacking visual notification coverage at the breakroom, one pull station is mounted too high, need account information set up at off site monitoring prior to site testing, HVAC units must to be in heat mode while testing duct detectors, discussed project schedule.
|
BLD07-00062
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:15:33 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD06-00704
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:15:17 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD06-00706
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:15:02 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD06-00705
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:14:42 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD06-00709
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:14:26 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD07-00061
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:14:08 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD06-00707
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:13:48 PM | A | PASS |
|
|
Fire life safety passed.
|
FIR09-00197
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:17:15 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00196
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:17:01 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00195
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:16:35 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00057
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:16:19 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00056
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:16:00 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00055
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:15:26 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00053
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:15:07 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00052
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:14:49 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
BLD04-01154
| FIRE-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:13:13 PM | P | PASS |
|
|
Building shell permit fire life safety okayed, see also previous inspection notes.
|
FIR09-00054
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 1:11:10 PM | P | FAIL |
|
|
Three pendent heads at the bathroom do not meet spacing requirements.
|
BLD06-00708
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 1:09:53 PM | A | FAIL |
|
|
Project related fire sprinkler permit is not approved for final.
|
FIR09-00428
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 12:01:36 PM | P | CANC |
|
|
Overbooked
|
FIR09-00427
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 12:01:09 PM | P | CANC |
|
|
Overbooked
|
FIR09-00426
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 12:00:42 PM | P | CANC |
|
|
Overbooked
|
FIR09-00425
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 12:00:08 PM | P | CANC |
|
|
Overbooked
|
BLD09-01099
| FIRE-Final Inspection | 7/21/2009 | 7/29/2009 | 7/29/2009 11:53:12 AM | A | PASS |
|
|
Fire life safety inspection completed acceptable, owner to repost max. occupant load sign when painting is finished.
|
FIR09-00370
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 11:51:00 AM | A | PASS |
|
|
Final walkthrough passed, fire sprinkler permit finaled.
|
FIR09-00371
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 11:09:30 AM | P | CANC |
|
|
Overbooked
|
BLD09-00871
| FIRE-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 10:52:17 AM | P | PASS |
|
|
Items on correction notice verified for completion, fire life safety passed.
|
FIR09-00432
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 10:49:00 AM | A | PASS |
|
|
Corrections are finished, fire sprinkler permit finaled.
|
FIR09-00192
| FIR-Aging Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 10:47:58 AM | | DONE |
|
|
Work in progress
|
FIR09-00411
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/28/2009 4:07:34 PM | P | CANC |
|
|
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
FIR09-00410
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/28/2009 4:06:56 PM | P | CANC |
|
|
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
FIR09-00409
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/28/2009 4:06:00 PM | P | CANC |
|
|
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|