Inspections for the day of: Wednesday, July 29, 2009.
Number of inspections: 35
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00164 INSP-Conference7/29/20097/29/20097/29/2009 5:20:01 PMPDONE
On site meeting with CM company, United Water, and Boise School district regarding backflow prevention device locations at the main fire riser.
FIR09-00260 INSP-Sprinkler Rough-in7/29/20097/29/20097/29/2009 5:15:41 PMPPART
Okay to cover hard lid ceilings at the mens and womens restrooms per red lines and initials on stamped plan set.
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/24/20097/29/20097/29/2009 5:13:46 PMAPART
Begin 24 hr. pneumatic testing for 8 preaction systems at the freezer area including rack and overhead systems-start time @ 4:00pm.
FIR09-00290 INSP-Final Inspection7/28/20097/29/20097/29/2009 5:10:59 PMAFAIL
Walkthrough completed for the dry goods warehouse and office areas, noted lacking visual notification coverage at the breakroom, one pull station is mounted too high, need account information set up at off site monitoring prior to site testing, HVAC units must to be in heat mode while testing duct detectors, discussed project schedule.
BLD07-00062 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:15:33 PMAPASS
Fire life safety passed.
BLD06-00704 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:15:17 PMAPASS
Fire life safety passed.
BLD06-00706 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:15:02 PMAPASS
Fire life safety passed.
BLD06-00705 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:14:42 PMAPASS
Fire life safety passed.
BLD06-00709 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:14:26 PMAPASS
Fire life safety passed.
BLD07-00061 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:14:08 PMAPASS
Fire life safety passed.
BLD06-00707 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:13:48 PMAPASS
Fire life safety passed.
FIR09-00197 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:17:15 PMPPASS
Fire sprinkler permit final approved.
FIR09-00196 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:17:01 PMPPASS
Fire sprinkler permit final approved.
FIR09-00195 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:16:35 PMPPASS
Fire sprinkler permit final approved.
FIR09-00057 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:16:19 PMPPASS
Fire sprinkler permit final approved.
FIR09-00056 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:16:00 PMPPASS
Fire sprinkler permit final approved.
FIR09-00055 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:15:26 PMPPASS
Fire sprinkler permit final approved.
FIR09-00053 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:15:07 PMPPASS
Fire sprinkler permit final approved.
FIR09-00052 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:14:49 PMPPASS
Fire sprinkler permit final approved.
BLD04-01154 FIRE-Final Inspection7/29/20097/29/20097/29/2009 1:13:13 PMPPASS
Building shell permit fire life safety okayed, see also previous inspection notes.
FIR09-00054 INSP-Final Inspection7/29/20097/29/20097/29/2009 1:11:10 PMPFAIL
Three pendent heads at the bathroom do not meet spacing requirements.
BLD06-00708 FIRE-Final Inspection7/28/20097/29/20097/29/2009 1:09:53 PMAFAIL
Project related fire sprinkler permit is not approved for final.
FIR09-00428 INSP-Final Inspection7/28/20097/29/20097/29/2009 12:01:36 PMPCANC
Overbooked
FIR09-00427 INSP-Final Inspection7/28/20097/29/20097/29/2009 12:01:09 PMPCANC
Overbooked
FIR09-00426 INSP-Final Inspection7/28/20097/29/20097/29/2009 12:00:42 PMPCANC
Overbooked
FIR09-00425 INSP-Final Inspection7/28/20097/29/20097/29/2009 12:00:08 PMPCANC
Overbooked
BLD09-01099 FIRE-Final Inspection7/21/20097/29/20097/29/2009 11:53:12 AMAPASS
Fire life safety inspection completed acceptable, owner to repost max. occupant load sign when painting is finished.
FIR09-00370 INSP-Final Inspection7/28/20097/29/20097/29/2009 11:51:00 AMAPASS
Final walkthrough passed, fire sprinkler permit finaled.
FIR09-00371 INSP-Final Inspection7/28/20097/29/20097/29/2009 11:09:30 AMPCANC
Overbooked
BLD09-00871 FIRE-Final Inspection7/29/20097/29/20097/29/2009 10:52:17 AMPPASS
Items on correction notice verified for completion, fire life safety passed.
FIR09-00432 INSP-Final Inspection7/29/20097/29/20097/29/2009 10:49:00 AMAPASS
Corrections are finished, fire sprinkler permit finaled.
FIR09-00192 FIR-Aging Inspection7/29/20097/29/20097/29/2009 10:47:58 AM DONE
Work in progress
FIR09-00411 INSP-Final Inspection7/28/20097/29/20097/28/2009 4:07:34 PMPCANC
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
FIR09-00410 INSP-Final Inspection7/28/20097/29/20097/28/2009 4:06:56 PMPCANC
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
FIR09-00409 INSP-Final Inspection7/28/20097/29/20097/28/2009 4:06:00 PMPCANC
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner