BLD09-00173
| FIRE-Conference | 7/29/2009 | 7/29/2009 | 7/30/2009 10:40:17 AM | P | DONE |
|
|
I discussed life safety items with the general contractor.
|
BLD08-01335
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/30/2009 9:26:51 AM | P | FAIL |
|
|
The project related fire alarm permit needs to be finaled. No life safety inspection was performed but I noted that the new north side fire hydrant 5" outlet is facing a new tree. One or the other needs to be relocated. If the fire hydrant is relocated the new location will have to be approved by resubmittal.
|
FIR08-00720
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/30/2009 8:44:37 AM | P | FAIL |
|
|
All of the initiating devices were tested but when it came time to verify signals nothing matched including the building address. All devices will need to be retested. All of the duct smoke detectors have been deleted as well as the dry pipe valve. As-builts are required. Strobe coverage is missing in the east lobby. It was addressed on the city approved plans but was not dealt with during installation. Strobe coverage had to be increased in a meeting room.
|
FIR08-00855
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/30/2009 7:42:20 AM | P | PASS |
|
|
Permit finaled
|
BLD09-00999
| FIRE-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 2:37:53 PM | P | PASS |
|
|
Life safety passed
|
BLD09-00837
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:27:30 PM | P | PASS |
|
|
Life safety passed.
|
FIR09-00417
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 2:26:18 PM | P | PASS |
|
|
permit finaled
|
FIR09-00399
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 2:25:49 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00444
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 2:25:13 PM | A | PASS |
|
|
Permit finaled
|
FIR09-00269
| FIR-Aging Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 10:19:46 AM | | NR |
|
|
work is in progress
|
BLD07-02129
| FIRE-Final Inspection | 7/28/2009 | 7/29/2009 | 7/29/2009 10:15:08 AM | A | FAIL |
|
|
There were no fire dept plan review notes with the approved plans but I performed a quick inspection anyway. The smoke alarms operated correctly and the building/apartment addresses were installed but the fire extinguishers were missing.
|
BLD09-00599
| FIRE-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 9:14:52 AM | P | PASS |
|
|
Life safety passed.
|
FIR09-00400
| INSP-Final Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 8:32:43 AM | P | PASS |
|
|
Permit finaled
|
FIR08-00720
| INSP-Final Inspection | 7/28/2009 | 7/29/2009 | 7/28/2009 9:06:45 AM | A | CANC |
|
|
Troy, Can we do this early in the morning? Please let me know as soon as possible, so I can set it up with the GC and the Sprinkler guys. Thanks, Jason ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|