Inspections for the day of: Wednesday, July 29, 2009.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00173 FIRE-Conference7/29/20097/29/20097/30/2009 10:40:17 AMPDONE
I discussed life safety items with the general contractor.
BLD08-01335 FIRE-Final Inspection7/28/20097/29/20097/30/2009 9:26:51 AMPFAIL
The project related fire alarm permit needs to be finaled. No life safety inspection was performed but I noted that the new north side fire hydrant 5" outlet is facing a new tree. One or the other needs to be relocated. If the fire hydrant is relocated the new location will have to be approved by resubmittal.
FIR08-00720 INSP-Final Inspection7/28/20097/29/20097/30/2009 8:44:37 AMPFAIL
All of the initiating devices were tested but when it came time to verify signals nothing matched including the building address. All devices will need to be retested. All of the duct smoke detectors have been deleted as well as the dry pipe valve. As-builts are required. Strobe coverage is missing in the east lobby. It was addressed on the city approved plans but was not dealt with during installation. Strobe coverage had to be increased in a meeting room.
FIR08-00855 INSP-Final Inspection7/28/20097/29/20097/30/2009 7:42:20 AMPPASS
Permit finaled
BLD09-00999 FIRE-Final Inspection7/29/20097/29/20097/29/2009 2:37:53 PMPPASS
Life safety passed
BLD09-00837 FIRE-Final Inspection7/28/20097/29/20097/29/2009 2:27:30 PMPPASS
Life safety passed.
FIR09-00417 INSP-Final Inspection7/29/20097/29/20097/29/2009 2:26:18 PMPPASS
permit finaled
FIR09-00399 INSP-Final Inspection7/29/20097/29/20097/29/2009 2:25:49 PMPPASS
Permit finaled
FIR09-00444 INSP-Final Inspection7/28/20097/29/20097/29/2009 2:25:13 PMAPASS
Permit finaled
FIR09-00269 FIR-Aging Inspection7/29/20097/29/20097/29/2009 10:19:46 AM NR
work is in progress
BLD07-02129 FIRE-Final Inspection7/28/20097/29/20097/29/2009 10:15:08 AMAFAIL
There were no fire dept plan review notes with the approved plans but I performed a quick inspection anyway. The smoke alarms operated correctly and the building/apartment addresses were installed but the fire extinguishers were missing.
BLD09-00599 FIRE-Final Inspection7/29/20097/29/20097/29/2009 9:14:52 AMPPASS
Life safety passed.
FIR09-00400 INSP-Final Inspection7/29/20097/29/20097/29/2009 8:32:43 AMPPASS
Permit finaled
FIR08-00720 INSP-Final Inspection7/28/20097/29/20097/28/2009 9:06:45 AMACANC
Troy, Can we do this early in the morning? Please let me know as soon as possible, so I can set it up with the GC and the Sprinkler guys. Thanks, Jason ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick