BLD11-01002
| FIRE-Final Inspection | 7/28/2011 | 7/29/2011 | 7/29/2011 4:39:28 PM | P | PASS |
|
|
Fire life safety okay for final pending keyed locking hardware is removed at the second exit- structural inspector to verify prior to final.
|
FIR11-00345
| INSP-Sprinkler Rough-in | 7/29/2011 | 7/29/2011 | 7/29/2011 4:36:27 PM | P | PART |
|
|
Field verified approved revised plans match installation. Cold cavity protection is satisfactory with the exception of one area at the main level study room #2. Contractor to repair prior to sheetrock cover. Overhead rough-in approved for cover.
|
FIR10-00137
| INSP-Final Inspection | 7/29/2011 | 7/29/2011 | 7/29/2011 4:32:30 PM | P | PART |
|
|
Remainder of correction items include; repair one non-functional H/S at the womens locker room sauna, repair notification device at the first floor family restroom, adjust cd setting at one appliance in the basement level womens locker room. Need to verify EOL voltage and reverify notification functionality at the cardio area.
|
BLD10-01036
| FIRE-Conference | 7/29/2011 | 7/29/2011 | 7/29/2011 4:27:38 PM | A | DONE |
|
|
Regarding project related fire alarm permit work.
|
FIR11-00340
| INSP-Final Inspection | 7/29/2011 | 7/29/2011 | 7/29/2011 4:27:00 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR11-00345
| INSP-Sprinkler Rough-in | 7/29/2011 | 7/29/2011 | 7/29/2011 12:00:00 AM | P | CANC |
|
|
ok to cover--Don Phone #: ###-####
|