Inspections for the day of: Friday, July 29, 2011.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00285 INSP-Sprinkler Rough-in7/29/20117/29/20118/1/2011 9:02:30 AMPPASS
Life safety passed
BLD11-00196 FIRE-Final Inspection7/28/20117/29/20117/29/2011 3:59:59 PMPFAIL
Repair the non functional emergency lights.
BLD11-00950 FIRE-Final Inspection7/29/20117/29/20117/29/2011 2:37:50 PMPPASS
life safety passed.
BLD11-00079 FIRE-Final Inspection7/28/20117/29/20117/29/2011 2:37:19 PMPFAIL
Need the missing exit discharge light bulb installed, the fire alarm and fire sprinkler pemits to be finaled.
FIR11-00359 INSP-Final Inspection7/29/20117/29/20117/29/2011 2:36:31 PMPFAIL
All items tested ok except the required smoke detector at the new NAC panel did not get installed.
FIR11-00359 INSP-Final Inspection7/29/20117/29/20117/29/2011 2:35:42 PMPFAIL
No city approved plans on site. No inspection performed.
FIR11-00372 INSP-Final Inspection7/28/20117/29/20117/29/2011 1:41:58 PMPPASS
Permit finaled. Hood suppression system operated correctly.
FIR11-00331 INSP-Final Inspection7/28/20117/29/20117/29/2011 9:57:52 AMAFAIL
No inspection performed because four of the five manual pull stations are mounted too high.
BLD11-00705 FIRE-Final Inspection7/28/20117/29/20117/29/2011 8:19:00 AMAFAIL
Del Phone #: ###-####. I left a message on the contacts phone. Arrived at the site 20 minutes later. No one there and doors locked. No inspection was performed.
BLD11-01732 FIRE-Final Inspection7/28/20117/29/20117/29/2011 8:15:28 AMAPASS
life safety passed