BLD12-03203
| FIRE-Final Inspection | 7/26/2013 | 7/29/2013 | 7/29/2013 4:58:34 PM | A | PART |
|
|
Final pending revised plan sheet for changes to the meeting rooms/hallway, missing exit discharge lighting, post signage at the fire riser and alarm panel rooms, project related fire alarm permit final also pending.
|
FIR13-00215
| INSP-Final Inspection | 7/26/2013 | 7/29/2013 | 7/29/2013 4:54:26 PM | P | PART |
|
|
Final pending as-built plans including accurate address points, additional duct SD, revised matrix, post map at the panel, provide record of completion forms. Functional testing passed.
|
FIR13-00116
| INSP-Final Inspection | 7/29/2013 | 7/29/2013 | 7/29/2013 4:51:25 PM | P | PASS |
|
|
Fire sprinkler work passed final walkthrough and inspection. Permit finaled.
|
FIR13-00324
| INSP-Final Inspection | 7/29/2013 | 7/29/2013 | 7/29/2013 4:50:14 PM | P | PASS |
|
|
Fire alarm work passed inspection. Permit finaled.
|
FIR13-00324
| INSP-Alarm Testing | 7/29/2013 | 7/29/2013 | 7/29/2013 4:49:02 PM | P | PASS |
|
|
Functional fire alarm testing completed.
|
BLD13-01351
| FIRE-Final Inspection | 7/29/2013 | 7/29/2013 | 7/29/2013 4:48:11 PM | P | PASS |
|
|
Life safety inspection completed acceptable.
|
BLD13-01352
| FIRE-Final Inspection | 7/29/2013 | 7/29/2013 | 7/29/2013 4:47:13 PM | P | PASS |
|
|
Life safety okayed. Contractor to repair one EM light at the south stairway per agreement.
|
BLD13-01350
| FIRE-Final Inspection | 7/29/2013 | 7/29/2013 | 7/29/2013 4:45:44 PM | P | PASS |
|
|
Life safety inspection passed.
|