Inspections for the day of: Wednesday, July 29, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02129 ELE-Aging Inspection7/29/20157/29/20157/31/2015 7:22:07 AM DONE
too busy
ELE13-01291 Electrical Rough-In7/29/20157/29/20157/29/2015 2:44:44 PMPCANC
Contact Frank Yantis for pole base rough in on Myrtle and 9th st. as close to 3:00 p.m. as possible please. Phone #: ###-#### Inspection requested via web by Tom Betty Tony called and cancelled this inspection
ELE14-03246 Electrical Rough-In7/28/20157/29/20157/29/2015 2:43:07 PMPFAIL
Levi. Tower 3 floors 4 ; 5 finals. Phone #: ###-#### Inspection requested via web by Sean DeLacy final ok for rms. 410 thru 415 and 510 thru 515 FAIL is for the appliances in these rooms being installed by appliance supplier wired incorrectly and not wired by electricans. The dryers have no connectors and nuetrals and grounds not being separated. Ranges have same problem. Asked ESI and RME to go back and check all appliances in complex now.
ELE14-01963 Electrical Rough-In7/29/20157/29/20157/29/2015 12:49:08 PMPPASS
Grid ceiling inspection in clubhouse. Phone #: ###-#### Inspection requested via web by Rafael Castillo r/i clubhouse and adjoining rms t bar ceilings ok to cover
GCE15-00092 GCE-Final7/28/20157/29/20157/29/2015 10:34:30 AMAFAIL
Erick ###-#### 422.52-GFCI required for drinking fountain. readily accessable or cir. breaker. strap 1/2" flex for make up air j box, disconnect or lockoff on breaker for hood exhaust fan
GCE15-00076 GCE-Final7/28/20157/29/20157/29/2015 9:39:36 AMAPASS
Terry ###-#### - code: 3484 final ok
GCE15-00055 GCE-Rough-In7/28/20157/29/20157/29/2015 8:55:54 AMAPASS
Ed ###-#### r/i garage and upst. ok