Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02317 Electrical Rough-In7/27/20157/29/20157/29/2015 4:25:25 PMPPASS
Underground and bonding for swimming pool Phone #: ###-#### Inspection requested via web by Lars Johnson rough-in ok cover underground conduits under concrete
ELE15-02337 Final7/28/20157/29/20157/29/2015 3:10:11 PMPFAIL
Kevin with Penske is the contact his cell no. is ###-#### or
Chris with Doherty Electric ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates NEC 110.24 shall post available AFC and date posted, NEC 250.53(G) Grounding electrode shall be installed at least 8ft. in contact with the soil. NEC 250.56 permanent services requires two ground rods unless 25 ohms or less of resistance
ELE15-02273 Electrical Rough-In7/29/20157/29/20157/29/2015 1:48:50 PMPPASS
Jay Phone #: ###-#### Rough-in ok cover addition
ELE15-02344 Permanent Service7/29/20157/29/20157/29/2015 1:16:22 PMPPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Date of posting AFC rating also required P/S U/G N OK