Inspections for the day of: Monday, July 29, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01333 Final7/29/20197/29/20197/29/2019 2:32:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher...
corrections made...ok to final
ELE19-00465 Final7/29/20197/29/20197/29/2019 2:07:21 PMPFAIL
call for gate access if not open Phone #: ###-#### Inspection requested via web by David Nelson...
1..Subpanel in fire riser room needs complete labelling
2..Subpanel in fire riser room needs energized
3..breaker for fire alarm system needs indicated
permanetly red and breaker lock out installed
4...outlets and switces more than1/4" recessed in sheetrock/tile need spark rings or extensions...various locations in kitchens
ELE19-02627 Final7/29/20197/29/20197/29/2019 12:34:05 PMPFAIL
Mike Phone #: ###-####....
work needs completed...recptacles and switch plates removed
ELE19-02790 Final7/26/20197/29/20197/29/2019 12:07:00 PMAPASS
inspection for existing door access circuit to new door access power supply and relocated outlet and data in mill work. Phone #: ###-#### Inspection requested via web by Deb Ipsen...
power was removed and reconnected using existing material just in different location of minimal distance...job complete and working..ok to final
ELE19-02745 Final7/26/20197/29/20197/29/2019 9:55:15 AMAPASS
Call ahead // Brian Phone #: ###-####...
correction made...ok to final
ELE19-02788 Electrical Rough-In7/28/20197/29/20197/29/2019 9:21:35 AMAPASS
Please call 30 mins prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton..
rough in of shop only...wall and ceiling cover
underground inspection and panel inspection needed in future
ELE19-02800 Final7/27/20197/29/20197/29/2019 9:08:34 AMACANC
i will be onsite between 10-11. please call ahead. Phone #: ###-#### >> Inspection requested via web by Taras Shulga Inspection cancelled from web by: Taras Shulga
ELE19-01198 Final7/26/20197/29/20197/29/2019 8:46:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher...ok to final
ELE18-02501 Final7/26/20197/29/20197/29/2019 8:46:16 AMPCANC
Only (1) free standing sign not two Phone #: ###-#### Inspection requested via web by Laurie Hoelscher...did inspection AM
ELE18-02501 Final7/26/20197/29/20197/29/2019 8:45:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher...ok to final
ELE19-02213 Permanent Service7/29/20197/29/20197/29/2019 8:34:27 AMAPASS
South end service. Phone #: ###-#### Inspection requested via web by Kevin Burke...
p/s u/g new ok 13 meters