Inspections for the day of: Thursday, July 3, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00583 FIR-Aging Inspection7/3/20037/3/20037/3/2003 12:00:00 AM PASS
Finaled by inspector 406 on 6/21/2001 7/3/2003 1:01:51 PM
BLD02-01924 FIRE-Final Inspection7/2/20037/3/20037/3/2003 12:00:00 AMAPASS
life safety finaled 7/2/2003 2:47:38 PM
FIR02-00459 INSP-Supply line flush7/2/20037/3/20037/3/2003 12:00:00 AMAPASS
Supply line flush is OK 7/3/2003 12:29:30 PM
BLD01-01537 BLD-Final7/2/20037/3/20037/3/2003 12:00:00 AMAPART
Temp given for grading and drainage permit. Sign off was for phase 1A. 7/2/2003 2:51:10 PM
FIR03-00251 INSP-Sprinkler Rough-in/Hydro7/3/20037/3/20037/3/2003 12:00:00 AMAFAIL
Sprinkler upright is spaced more than 7'-6" off the office wall. Sprinkler riser needs inspected still. 7/3/2003 12:36:27 PM
FIR02-00432 INSP-Final Inspection7/2/20037/3/20037/3/2003 12:00:00 AMPFAIL
Project not ready for a final inspection yet. Underground supply flush was OK though 7/3/2003 4:06:59 PM
FIR02-00459 INSP-Sprinkler Rough-in/Hydro7/3/20037/3/20037/3/2003 12:00:00 AMPPART
items on the approved plans have been corrected in areas "C" and "D". Sprinkler rough-in in area "A" and "B" is OK
FIR03-00251 INSP-Sprinkler Rough-in/Hydro7/3/20037/3/20037/3/2003 12:00:00 AMPPASS
Underground supply line hydro is ok
BLD03-00301 FIRE-Final Inspection7/3/20037/3/20037/3/2003 12:00:00 AMPPASS
Fire alarm, fire sprinkler and fire life safety finaled. Fire alarm system is complete
BLD02-02390 FIRE-Final Inspection7/3/20037/3/20037/3/2003 12:00:00 AMPPASS
Fire alarm, fire sprinkler and fire life safety finaled. Fire alarm system is complete