Inspections for the day of: Monday, July 3, 2006.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02371 Electrical Rough-In7/3/20067/3/20067/3/2006 4:26:15 PMPFAIL
tim - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left corr notice, nec 300.4(A)&(D) edgr of holes and nm cable shall be 1 1/4" from edge of framing members,314.20 in walls of combustible material, box shall be flush with finished surface,334.30 nm cable shall be stapled within 12" of box and every 4 1/2', 250.86 metal boxes shall be grounded, 334.80 2 or more nm cables in hole to be draft stopped shall be derated per 310.15(B)(2)(a), BCC all make-up shall be done
ELE06-01925 Permanent Service7/3/20067/3/20067/3/2006 3:38:52 PMPFAIL
ramiz; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left correction notice, nec 210.70(A)(2)(b) lighting outlet shall be at outside for door at grade level, 314.15(A) emt connectors shall be listed for use in wet locations
ELE06-02423 Final7/3/20067/3/20067/3/2006 3:01:06 PMPDONE
Phone #: ###-#### Internet Inspection Request from: Paul Schepper see t/s
ELE06-02423 Temporary Service7/3/20067/3/20067/3/2006 3:00:27 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Paul Schepper t/s u/g n ok
ELE06-02472 Final6/30/20067/3/20067/3/2006 2:56:26 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-01438 ELE-Aging Inspection7/3/20067/3/20067/3/2006 2:45:53 PM DONE
suc
ELE06-02477 Rough-In Permanent Service7/3/20067/3/20067/3/2006 2:40:24 PMPPASS
Scheduled by a contractor via Hello! on 7/3/2006 at 7:31:50 AM. Contact: ###-####. ric ok, p/s u/g n ok
ELE06-02479 Permanent Service7/3/20067/3/20067/3/2006 1:58:52 PMPPASS
PLEASE CALL BEN McDONNAGH, HE IS AT THE JOBSITE & HOPING TO RESTORE POWER TO THIS HOME YET TODAY.; Phone #: ###-#### Internet Inspection Request from: Randy Vail p/s o/h rec ok
ELE06-02422 Final7/3/20067/3/20067/3/2006 12:59:52 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Paul Schepper see t/s
ELE06-02422 Temporary Service7/3/20067/3/20067/3/2006 12:59:21 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Paul Schepper t/s u/g n ok
ELE06-01627 Electrical Rough-In6/30/20067/3/20067/3/2006 11:07:13 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton wrong permit and nr
ELE06-02429 Electrical Rough-In7/3/20067/3/20067/3/2006 11:06:13 AMPPART
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls except front entry and ceilings ok to cover
ELE05-04393 Final6/30/20067/3/20067/3/2006 10:22:27 AMAPASS
FINAL INSPECTION Alt Phone ###-#### (Kelly) ###-#### (Rick ); Phone #: ###-#### Internet Inspection Request from: Cathy Felin called left message, left survey, nec 408.4 all breakers shall be clearly labelled
ELE06-02473 Electrical Rough-In6/30/20067/3/20067/3/2006 9:45:39 AMAPASS
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric kitchen ok
ELE06-01636 Final6/30/20067/3/20067/3/2006 9:06:18 AMANH
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, no access, will recall
ELE05-04213 Final6/30/20067/3/20067/3/2006 8:48:01 AMAPASS
Scheduled by a contractor via Hello! on 6/30/2006 at 1:21:40 PM. Contact: ###-####. ok to final
ELE06-02470 Electrical Rough-In6/30/20067/3/20067/3/2006 8:46:50 AMACANC
mike; Phone #: ###-#### sp 64 Internet Inspection Request from: Cathy Chiles see final
ELE06-02470 Final7/3/20067/3/20067/3/2006 8:46:15 AMAPASS
mike; Phone #: ###-#### sp 64 Internet Inspection Request from: Cathy Chiles see rip, ok to final
ELE06-02470 Rough-In Permanent Service7/3/20067/3/20067/3/2006 8:45:31 AMAPASS
mike; Phone #: ###-#### sp 64 Internet Inspection Request from: Cathy Chiles talked to contr, told to get address on bldg, ok to cover u/g, p/s u/g rec ok
ELE06-02440 Electrical Rough-In6/30/20067/3/20067/3/2006 8:18:25 AMAFAIL
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, service ok, but not on inspection request, NEC 210.52(A) recpts shall be installed within 6' of room opening(mbr), top of stairs south wall, BCC all make-up shall be done, garage lights, range box