ELE06-02371
| Electrical Rough-In | 7/3/2006 | 7/3/2006 | 7/3/2006 4:26:15 PM | P | FAIL |
|
|
tim - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left corr notice, nec 300.4(A)&(D) edgr of holes and nm cable shall be 1 1/4" from edge of framing members,314.20 in walls of combustible material, box shall be flush with finished surface,334.30 nm cable shall be stapled within 12" of box and every 4 1/2', 250.86 metal boxes shall be grounded, 334.80 2 or more nm cables in hole to be draft stopped shall be derated per 310.15(B)(2)(a), BCC all make-up shall be done
|
ELE06-01925
| Permanent Service | 7/3/2006 | 7/3/2006 | 7/3/2006 3:38:52 PM | P | FAIL |
|
|
ramiz; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left correction notice, nec 210.70(A)(2)(b) lighting outlet shall be at outside for door at grade level, 314.15(A) emt connectors shall be listed for use in wet locations
|
ELE06-02423
| Final | 7/3/2006 | 7/3/2006 | 7/3/2006 3:01:06 PM | P | DONE |
|
|
Phone #: ###-#### Internet Inspection Request from: Paul Schepper see t/s
|
ELE06-02423
| Temporary Service | 7/3/2006 | 7/3/2006 | 7/3/2006 3:00:27 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Paul Schepper t/s u/g n ok
|
ELE06-02472
| Final | 6/30/2006 | 7/3/2006 | 7/3/2006 2:56:26 PM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
|
ELE06-01438
| ELE-Aging Inspection | 7/3/2006 | 7/3/2006 | 7/3/2006 2:45:53 PM | | DONE |
|
|
suc
|
ELE06-02477
| Rough-In Permanent Service | 7/3/2006 | 7/3/2006 | 7/3/2006 2:40:24 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/3/2006 at 7:31:50 AM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE06-02479
| Permanent Service | 7/3/2006 | 7/3/2006 | 7/3/2006 1:58:52 PM | P | PASS |
|
|
PLEASE CALL BEN McDONNAGH, HE IS AT THE JOBSITE & HOPING TO RESTORE POWER TO THIS HOME YET TODAY.; Phone #: ###-#### Internet Inspection Request from: Randy Vail p/s o/h rec ok
|
ELE06-02422
| Final | 7/3/2006 | 7/3/2006 | 7/3/2006 12:59:52 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Paul Schepper see t/s
|
ELE06-02422
| Temporary Service | 7/3/2006 | 7/3/2006 | 7/3/2006 12:59:21 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Paul Schepper t/s u/g n ok
|
ELE06-01627
| Electrical Rough-In | 6/30/2006 | 7/3/2006 | 7/3/2006 11:07:13 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton wrong permit and nr
|
ELE06-02429
| Electrical Rough-In | 7/3/2006 | 7/3/2006 | 7/3/2006 11:06:13 AM | P | PART |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls except front entry and ceilings ok to cover
|
ELE05-04393
| Final | 6/30/2006 | 7/3/2006 | 7/3/2006 10:22:27 AM | A | PASS |
|
|
FINAL INSPECTION Alt Phone ###-#### (Kelly) ###-#### (Rick ); Phone #: ###-#### Internet Inspection Request from: Cathy Felin called left message, left survey, nec 408.4 all breakers shall be clearly labelled
|
ELE06-02473
| Electrical Rough-In | 6/30/2006 | 7/3/2006 | 7/3/2006 9:45:39 AM | A | PASS |
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric kitchen ok
|
ELE06-01636
| Final | 6/30/2006 | 7/3/2006 | 7/3/2006 9:06:18 AM | A | NH |
|
|
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, no access, will recall
|
ELE05-04213
| Final | 6/30/2006 | 7/3/2006 | 7/3/2006 8:48:01 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/30/2006 at 1:21:40 PM. Contact: ###-####. ok to final
|
ELE06-02470
| Electrical Rough-In | 6/30/2006 | 7/3/2006 | 7/3/2006 8:46:50 AM | A | CANC |
|
|
mike; Phone #: ###-#### sp 64 Internet Inspection Request from: Cathy Chiles see final
|
ELE06-02470
| Final | 7/3/2006 | 7/3/2006 | 7/3/2006 8:46:15 AM | A | PASS |
|
|
mike; Phone #: ###-#### sp 64 Internet Inspection Request from: Cathy Chiles see rip, ok to final
|
ELE06-02470
| Rough-In Permanent Service | 7/3/2006 | 7/3/2006 | 7/3/2006 8:45:31 AM | A | PASS |
|
|
mike; Phone #: ###-#### sp 64 Internet Inspection Request from: Cathy Chiles talked to contr, told to get address on bldg, ok to cover u/g, p/s u/g rec ok
|
ELE06-02440
| Electrical Rough-In | 6/30/2006 | 7/3/2006 | 7/3/2006 8:18:25 AM | A | FAIL |
|
|
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, service ok, but not on inspection request, NEC 210.52(A) recpts shall be installed within 6' of room opening(mbr), top of stairs south wall, BCC all make-up shall be done, garage lights, range box
|