Inspections for the day of: Monday, July 3, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01235 FIRE-Final Inspection7/3/20067/3/20067/3/2006 3:25:32 PMPPART
Life safety c/n items from previous inspection have been completed. Project related fire alarm work is not yet completed, the FA panel has been verified for functionality per conditions of temproary occupancy request. Project related fire sprinkler work is not completed pending application and issuance of a fire sprinkler permit to perform required corrections. BLD final pending alarm and sprinkler permit finals.
FIR05-00755 INSP-Final Inspection6/29/20067/3/20067/3/2006 3:18:34 PMPPASS
Items on correction notice per previous inspection have been verified for completion, final field inspection passed, alarm permit finaled.
FIR06-00474 INSP-Sprinkler Rough-in6/30/20067/3/20067/3/2006 1:20:38 PMAPART
Preliminary alarm inspection to verify functionality of the new FA panel. Alarm work per the scope of the permit is not yet completed at this time. Testing done today included panel batteries, phone lines, tampers at riser, wet flow, outside bell, and signal verification. AC power loss did not report to monitoring company as required, also need to provide a lock at the breaker. Remainder of alarm work to be tested at next inspection.
BLD06-00538 FIRE-Conference6/30/20067/3/20067/3/2006 12:47:03 PMADONE
On site visit with general contractor to discuss location of pfe's and requirements of fire code review notes.
BLD06-00537 FIRE-Conference6/30/20067/3/20067/3/2006 12:44:03 PMADONE
On site visit to discuss fire extinguisher locations and requirements of fire code review notes.
BLD06-00485 FIRE-Final Inspection6/30/20067/3/20067/3/2006 10:58:12 AMAPASS
Correction item has been completed, fire life safety inspection passed.
BLD05-03413 FIRE-Final Inspection6/30/20067/3/20067/3/2006 12:00:00 AMACANC
not ready per raylene -joe; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley