ELE07-02033
| Final | 7/3/2007 | 7/3/2007 | 7/3/2007 3:50:02 PM | P | PASS |
|
|
mike Phone #: ###-#### oik
|
ELE07-02358
| Rough-In Permanent Service | 7/2/2007 | 7/3/2007 | 7/3/2007 3:30:55 PM | P | PASS |
|
|
john Phone #: ###-#### r/i p/s u/g new ok
|
ELE07-02367
| Permanent Service | 7/3/2007 | 7/3/2007 | 7/3/2007 3:02:27 PM | P | FAIL |
|
|
Service Insp. Thank you!! Todd - ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr. called 250.24(C) needs neutral from meter to p/s disconnect, 110.2 pump side pack not listed , only thing listed is the jbox and control cabinet
|
ELE07-02346
| Conference | 7/3/2007 | 7/3/2007 | 7/3/2007 2:41:00 PM | P | DONE |
|
|
greg; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok
|
ELE07-02368
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 2:19:15 PM | P | PART |
|
|
louis - underground; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang u/g only ok
|
ELE07-02064
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 1:52:10 PM | P | PART |
|
|
jared; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang u/g area A anop
|
ELE07-02367
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 12:47:59 PM | P | CANC |
|
|
Service Inspection Please. Thank you. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|
ELE07-00988
| Final | 7/2/2007 | 7/3/2007 | 7/3/2007 12:43:12 PM | A | FAIL |
|
|
eric Phone #: ###-#### corr. called 110.3(B) use manufactures listed breakers only
|
ELE07-02230
| Final | 7/2/2007 | 7/3/2007 | 7/3/2007 10:34:14 AM | A | PASS |
|
|
dennis Phone #: ###-#### ok
|
ELE07-02230
| Temporary Service | 7/3/2007 | 7/3/2007 | 7/3/2007 10:31:16 AM | P | PASS |
|
|
dennis Phone #: ###-#### t/s u/g new ok
|
ELE07-02362
| Temporary Service | 7/2/2007 | 7/3/2007 | 7/3/2007 10:12:58 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange t/s u/g N ok
|
ELE07-02361
| Temporary Service | 7/2/2007 | 7/3/2007 | 7/3/2007 10:12:34 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange t/s u/g N ok
|
ELE07-02357
| Electrical Rough-In | 7/2/2007 | 7/3/2007 | 7/3/2007 9:35:50 AM | A | PART |
|
|
wet niche Phone #: ###-#### Internet Inspection Request from: DJ Carman u/g to pool light and potting ok only
|
ELE07-02326
| Rough-In Permanent Service | 7/2/2007 | 7/3/2007 | 7/3/2007 9:16:49 AM | A | FAIL |
|
|
zane Phone #: ###-#### see added p/s , r/i failed install for boxes, complete all makeup outsie boxes, 334.23 protect all cables high and low volt by attic accesses, 300.4(A)(1)&(D) nail plates and 11/4" for low voltage, 110.2 Jtub not listed by testing lab called
|
ELE07-02326
| Permanent Service | 7/3/2007 | 7/3/2007 | 7/3/2007 9:13:44 AM | A | PASS |
|
|
zane Phone #: ###-#### p/s u/g new ok
|
ELE07-02287
| Electrical Rough-In | 7/2/2007 | 7/3/2007 | 7/3/2007 8:17:10 AM | A | PASS |
|
|
trench inspection first thing please Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer u/g for street lights
|