ELE07-02370
| Temporary Service | 7/3/2007 | 7/3/2007 | 7/3/2007 3:55:30 PM | P | FAIL |
|
|
ed Phone #: ###-#### called, left corr notice, nec 110.14(A) ground connection shall be properly installed to ensure a thoroughly good connection
|
ELE07-02369
| Temporary Service | 7/3/2007 | 7/3/2007 | 7/3/2007 3:34:17 PM | P | FAIL |
|
|
ed Phone #: ###-#### called contr, left corr notice, nec 110.14(A) ground connections shall be thoroughly made
|
ELE07-02351
| Conference | 7/2/2007 | 7/3/2007 | 7/3/2007 3:02:59 PM | P | DONE |
|
|
James ###-#### talked about inside wiring for new storage building or shop, owner said service will be by others, said to watch for 1 1/4" make-up free conductor length, told owner if only 1 recpt on 20a ckt, then shall have 20a recpt, but if more than one recpt, can be 15a
|
ELE07-01601
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 2:39:13 PM | P | FAIL |
|
|
Grid inspection for cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections not made, called contractor, left message, read passge on independent support wires, signed corr notice 2nd time
|
ELE07-02110
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 2:34:24 PM | P | PASS |
|
|
jason Phone #: ###-#### ric ok
|
ELE07-01011
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 1:42:12 PM | P | CANC |
|
|
underground to meter Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called contr and said that utility does inspection to meter
|
ELE07-02235
| Rough-In Permanent Service | 7/3/2007 | 7/3/2007 | 7/3/2007 1:40:30 PM | P | CANC |
|
|
also underground to meter Phone #: ###-#### Internet Inspection Request from: Brandon Blackham see ri, wrong type request
|
ELE07-02235
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 1:40:05 PM | P | PASS |
|
|
also underground to meter Phone #: ###-#### Internet Inspection Request from: Brandon Blackham correction made ri for house only ok, called contr and said utility does inspection to meter
|
ELE07-01065
| Temporary Service | 7/3/2007 | 7/3/2007 | 7/3/2007 1:38:13 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made t/s o/h n ok
|
ELE07-01178
| Final | 7/2/2007 | 7/3/2007 | 7/3/2007 1:18:53 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called, left corr notice, nec 210.52(A)(2) shall install recpt in 2' wall in north bedroom, 352.30(A) shall strap rnc at panel within 3' of termination, 110.22 shall label garage disconnect and tell off-on on label, 410.8(A) closet light below stairs shall be 12" from shelving to edge of fixture, 210.8(A)(3) front and bath gfci shall operate correctly, 110.3(B) listed equip shall be installed per instructions i.e. kitchen and laundry recpts have open neutrals
|
ELE07-01568
| Final | 7/2/2007 | 7/3/2007 | 7/3/2007 11:05:02 AM | A | PASS |
|
|
alan Phone #: ###-#### ok to final
|
ELE07-02211
| Rough-In Permanent Service | 7/2/2007 | 7/3/2007 | 7/3/2007 10:19:40 AM | A | PASS |
|
|
Contact Shane Vanleuven re-inspect for service and mech. room that failed. Phone #: ###-#### Internet Inspection Request from: Debby Ellis ric mech room ok, corrections made, p/s o/h rec ok
|
ELE07-00769
| Rough-In Permanent Service | 7/3/2007 | 7/3/2007 | 7/3/2007 9:54:43 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/3/2007 at 6:58:58 AM. Contact: ###-####. ri for service ok, p/s u/g n ok
|
ELE07-00768
| Rough-In Permanent Service | 7/3/2007 | 7/3/2007 | 7/3/2007 9:35:59 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/3/2007 at 6:57:50 AM. Contact: ###-####. ri ok for service, p/s u/g n ok
|
ELE07-02339
| Electrical Rough-In | 7/2/2007 | 7/3/2007 | 7/3/2007 9:12:15 AM | A | PASS |
|
|
Walls, cover inspection. Please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson walls and hard lids ok to cover
|
ELE07-02286
| Electrical Rough-In | 7/2/2007 | 7/3/2007 | 7/3/2007 9:07:59 AM | A | PASS |
|
|
building will be open at 8:00 a. m. Call Steve at ###-#### if there are any questions. Internet Inspection Request from: Steve Craig walls only ok to cover, called to post address
|
ELE07-02285
| Electrical Rough-In | 7/2/2007 | 7/3/2007 | 7/3/2007 8:44:20 AM | A | PASS |
|
|
Building will be unlicked at 8:00 a.m. Call Steve at ###-#### if there are any questions. Phone #: ###-#### Internet Inspection Request from: Steve Craig walls only ok to cover, called for address to be posted
|
ELE07-01601
| Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 8:21:51 AM | A | FAIL |
|
|
need grid inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections not made, fee due
|
ELE07-02063
| Rough-In Permanent Service | 7/3/2007 | 7/3/2007 | 7/3/2007 7:56:44 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/3/2007 at 6:33:23 AM. Contact: ###-####. ri for service ok, p/s, exst meter pak, n, ok
|