Inspections for the day of: Tuesday, July 3, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02370 Temporary Service7/3/20077/3/20077/3/2007 3:55:30 PMPFAIL
ed Phone #: ###-#### called, left corr notice, nec 110.14(A) ground connection shall be properly installed to ensure a thoroughly good connection
ELE07-02369 Temporary Service7/3/20077/3/20077/3/2007 3:34:17 PMPFAIL
ed Phone #: ###-#### called contr, left corr notice, nec 110.14(A) ground connections shall be thoroughly made
ELE07-02351 Conference7/2/20077/3/20077/3/2007 3:02:59 PMPDONE
James ###-#### talked about inside wiring for new storage building or shop, owner said service will be by others, said to watch for 1 1/4" make-up free conductor length, told owner if only 1 recpt on 20a ckt, then shall have 20a recpt, but if more than one recpt, can be 15a
ELE07-01601 Electrical Rough-In7/3/20077/3/20077/3/2007 2:39:13 PMPFAIL
Grid inspection for cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections not made, called contractor, left message, read passge on independent support wires, signed corr notice 2nd time
ELE07-02110 Electrical Rough-In7/3/20077/3/20077/3/2007 2:34:24 PMPPASS
jason Phone #: ###-#### ric ok
ELE07-01011 Electrical Rough-In7/3/20077/3/20077/3/2007 1:42:12 PMPCANC
underground to meter Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called contr and said that utility does inspection to meter
ELE07-02235 Rough-In Permanent Service7/3/20077/3/20077/3/2007 1:40:30 PMPCANC
also underground to meter Phone #: ###-#### Internet Inspection Request from: Brandon Blackham see ri, wrong type request
ELE07-02235 Electrical Rough-In7/3/20077/3/20077/3/2007 1:40:05 PMPPASS
also underground to meter Phone #: ###-#### Internet Inspection Request from: Brandon Blackham correction made ri for house only ok, called contr and said utility does inspection to meter
ELE07-01065 Temporary Service7/3/20077/3/20077/3/2007 1:38:13 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made t/s o/h n ok
ELE07-01178 Final7/2/20077/3/20077/3/2007 1:18:53 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called, left corr notice, nec 210.52(A)(2) shall install recpt in 2' wall in north bedroom, 352.30(A) shall strap rnc at panel within 3' of termination, 110.22 shall label garage disconnect and tell off-on on label, 410.8(A) closet light below stairs shall be 12" from shelving to edge of fixture, 210.8(A)(3) front and bath gfci shall operate correctly, 110.3(B) listed equip shall be installed per instructions i.e. kitchen and laundry recpts have open neutrals
ELE07-01568 Final7/2/20077/3/20077/3/2007 11:05:02 AMAPASS
alan Phone #: ###-#### ok to final
ELE07-02211 Rough-In Permanent Service7/2/20077/3/20077/3/2007 10:19:40 AMAPASS
Contact Shane Vanleuven re-inspect for service and mech. room that failed. Phone #: ###-#### Internet Inspection Request from: Debby Ellis ric mech room ok, corrections made, p/s o/h rec ok
ELE07-00769 Rough-In Permanent Service7/3/20077/3/20077/3/2007 9:54:43 AMAPASS
Scheduled by a contractor via Hello! on 7/3/2007 at 6:58:58 AM. Contact: ###-####. ri for service ok, p/s u/g n ok
ELE07-00768 Rough-In Permanent Service7/3/20077/3/20077/3/2007 9:35:59 AMAPASS
Scheduled by a contractor via Hello! on 7/3/2007 at 6:57:50 AM. Contact: ###-####. ri ok for service, p/s u/g n ok
ELE07-02339 Electrical Rough-In7/2/20077/3/20077/3/2007 9:12:15 AMAPASS
Walls, cover inspection. Please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson walls and hard lids ok to cover
ELE07-02286 Electrical Rough-In7/2/20077/3/20077/3/2007 9:07:59 AMAPASS
building will be open at 8:00 a. m. Call Steve at ###-#### if there are any questions. Internet Inspection Request from: Steve Craig walls only ok to cover, called to post address
ELE07-02285 Electrical Rough-In7/2/20077/3/20077/3/2007 8:44:20 AMAPASS
Building will be unlicked at 8:00 a.m. Call Steve at ###-#### if there are any questions. Phone #: ###-#### Internet Inspection Request from: Steve Craig walls only ok to cover, called for address to be posted
ELE07-01601 Electrical Rough-In7/3/20077/3/20077/3/2007 8:21:51 AMAFAIL
need grid inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections not made, fee due
ELE07-02063 Rough-In Permanent Service7/3/20077/3/20077/3/2007 7:56:44 AMAPASS
Scheduled by a contractor via Hello! on 7/3/2007 at 6:33:23 AM. Contact: ###-####. ri for service ok, p/s, exst meter pak, n, ok