Inspections for the day of: Tuesday, July 3, 2007.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00958 INSP-Sprinkler Rough-in/Hydro7/2/20077/3/20077/5/2007 10:02:56 AMPPASS
I finished a hydro and overhead rough to cover inspection at Bonaventure Bldg. B
FIR06-00466 INSP-Final Inspection7/2/20077/3/20077/3/2007 4:49:59 PMPFAIL
The east riser flow switch still did not operate and the company that was to perform the manometer test did not show up.
FIR07-00461 INSP-Sprinkler Rough-in7/3/20077/3/20077/3/2007 4:46:46 PMPPASS
5'0" underground stub out is ok to cover
FIR07-00097 INSP-Final Inspection7/3/20077/3/20077/3/2007 3:03:05 PMPPASS
permit finaled. installation matches the resubmitted plans.
BLD07-00918 FIRE-Final Inspection7/3/20077/3/20077/3/2007 3:01:59 PMPPASS
Life safety passed.
FIR07-00484 INSP-Sprinkler Rough-in7/2/20077/3/20077/3/2007 12:38:06 PMAFAIL
The bury depth of the underground piping does not meet the minumum 4'6" bury depth. Since the next inspection will be the third I have applied a re-inspection fee
MIS07-00146 FIR-Final6/29/20077/3/20077/3/2007 11:39:44 AMAPART
A temporary occupancy was given until the approved door hardware is installed and the thumbturns removed. This applies to all of the tenant exit doors in the egress corridor.