FIR08-00410
| INSP-Sprinkler Rough-in | 7/3/2008 | 7/3/2008 | 7/3/2008 4:49:40 PM | P | PART |
|
|
UG fire supply line installation is approved for cover.
|
FIR08-00415
| INSP-Sprinkler Rough-in | 7/3/2008 | 7/3/2008 | 7/3/2008 3:52:32 PM | P | PART |
|
|
Overhead system modifications approved for cover at the drop ceilings, QR heads provided.
|
FIR08-00414
| INSP-Sprinkler Rough-in | 7/3/2008 | 7/3/2008 | 7/3/2008 3:49:31 PM | P | PART |
|
|
Scope of overhead permit work completed okay, minor field modifications with regard to sprinkler location approved, final pending field tile and escutcheons.
|
FIR08-00312
| INSP-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 2:01:33 PM | A | PASS |
|
|
Fire alarm inspection completed. Candella in living room and family room were changed to 75cd. Inspection and completion forms were signed and will be faxed to PDS fire on 7/7/08. KR
|
FIR08-00109
| INSP-Final Inspection | 7/3/2008 | 7/3/2008 | 7/3/2008 1:49:56 PM | A | PASS |
|
|
C/N items are complete, final fire alarm test passed, permit finaled.
|
BLD06-01992
| FIRE-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 11:55:50 AM | A | FAIL |
|
|
Smoke alarms at each unit must meet installation guidelines per NFPA 72 chapter 11, also see fire code review notes on approved plan set for details.
|
BLD06-01994
| FIRE-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 11:53:45 AM | A | FAIL |
|
|
Smoke alarms at units 2235, 2243 and 2249 are in need of adjustment due to spacing requirements not met per NFPA 72 ch. 11 including proximity to bathroom doors, HVAC registers, spacing outside of sleeping areas, one missing smoke alarm. See fire code review notes attatched to the approved plan set for details. Remainder of fire life safety issues are acceptable.
|
FIR08-00218
| FIR-Aging Inspection | 7/3/2008 | 7/3/2008 | 7/3/2008 11:51:07 AM | | NR |
|
|
Talked With Matt Casey, job is not ready for inspection.KR
|
BLD08-00659
| FIRE-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 11:48:14 AM | A | FAIL |
|
|
Noted project related fire sprinkler permit has not been issued and must be approved and finaled prior to building life safety final, noted heads improperly spaced above the new stairway. Reviewed additional items with the contractor including where to post two required fire extinguishers, door hardware at the second exit main level, EM lights and exit signs tested okay, stairway handrails under repair.
|
BLD08-00118
| FIRE-Final Inspection | 7/3/2008 | 7/3/2008 | 7/3/2008 11:46:12 AM | P | FAIL |
|
|
Bathroom door hardware has not been changed and suite number has not been installed. See notes per last inspection.Contractor wanted inspector to come back late afternoon. There will be no entry to this suite until monday due to wood floors being finished.KR
|
BLD06-02892
| FIRE-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 11:43:29 AM | A | FAIL |
|
|
Gate hardware at the pool enclosure must comply with IFC chapter 10 sec. 1004.8 regarding means of egress, padlocks are not compliant.
|
BLD08-00797
| FIRE-Final Inspection | 7/3/2008 | 7/3/2008 | 7/3/2008 11:22:03 AM | P | PASS |
|
|
All corrections were made per last inspection notes. KR
|
FIR08-00214
| INSP-Sprinkler Rough-in/Hydro | 7/2/2008 | 7/3/2008 | 7/3/2008 11:08:55 AM | A | FAIL |
|
|
Hydro test failed gauge dropped 4 psi. Overhead OK to cover. KR
|
BLD08-01001
| FIRE-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 10:10:09 AM | A | PASS |
|
|
Fire life safety completed. KR
|
BLD08-00502
| FIRE-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 9:32:42 AM | P | PASS |
|
|
All corrections made per last inspection. KR
|