Inspections for the day of: Thursday, July 3, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00410 INSP-Sprinkler Rough-in7/3/20087/3/20087/3/2008 4:49:40 PMPPART
UG fire supply line installation is approved for cover.
FIR08-00415 INSP-Sprinkler Rough-in7/3/20087/3/20087/3/2008 3:52:32 PMPPART
Overhead system modifications approved for cover at the drop ceilings, QR heads provided.
FIR08-00414 INSP-Sprinkler Rough-in7/3/20087/3/20087/3/2008 3:49:31 PMPPART
Scope of overhead permit work completed okay, minor field modifications with regard to sprinkler location approved, final pending field tile and escutcheons.
FIR08-00312 INSP-Final Inspection7/2/20087/3/20087/3/2008 2:01:33 PMAPASS
Fire alarm inspection completed. Candella in living room and family room were changed to 75cd. Inspection and completion forms were signed and will be faxed to PDS fire on 7/7/08. KR
FIR08-00109 INSP-Final Inspection7/3/20087/3/20087/3/2008 1:49:56 PMAPASS
C/N items are complete, final fire alarm test passed, permit finaled.
BLD06-01992 FIRE-Final Inspection7/2/20087/3/20087/3/2008 11:55:50 AMAFAIL
Smoke alarms at each unit must meet installation guidelines per NFPA 72 chapter 11, also see fire code review notes on approved plan set for details.
BLD06-01994 FIRE-Final Inspection7/2/20087/3/20087/3/2008 11:53:45 AMAFAIL
Smoke alarms at units 2235, 2243 and 2249 are in need of adjustment due to spacing requirements not met per NFPA 72 ch. 11 including proximity to bathroom doors, HVAC registers, spacing outside of sleeping areas, one missing smoke alarm. See fire code review notes attatched to the approved plan set for details. Remainder of fire life safety issues are acceptable.
FIR08-00218 FIR-Aging Inspection7/3/20087/3/20087/3/2008 11:51:07 AM NR
Talked With Matt Casey, job is not ready for inspection.KR
BLD08-00659 FIRE-Final Inspection7/2/20087/3/20087/3/2008 11:48:14 AMAFAIL
Noted project related fire sprinkler permit has not been issued and must be approved and finaled prior to building life safety final, noted heads improperly spaced above the new stairway. Reviewed additional items with the contractor including where to post two required fire extinguishers, door hardware at the second exit main level, EM lights and exit signs tested okay, stairway handrails under repair.
BLD08-00118 FIRE-Final Inspection7/3/20087/3/20087/3/2008 11:46:12 AMPFAIL
Bathroom door hardware has not been changed and suite number has not been installed. See notes per last inspection.Contractor wanted inspector to come back late afternoon. There will be no entry to this suite until monday due to wood floors being finished.KR
BLD06-02892 FIRE-Final Inspection7/2/20087/3/20087/3/2008 11:43:29 AMAFAIL
Gate hardware at the pool enclosure must comply with IFC chapter 10 sec. 1004.8 regarding means of egress, padlocks are not compliant.
BLD08-00797 FIRE-Final Inspection7/3/20087/3/20087/3/2008 11:22:03 AMPPASS
All corrections were made per last inspection notes. KR
FIR08-00214 INSP-Sprinkler Rough-in/Hydro7/2/20087/3/20087/3/2008 11:08:55 AMAFAIL
Hydro test failed gauge dropped 4 psi. Overhead OK to cover. KR
BLD08-01001 FIRE-Final Inspection7/2/20087/3/20087/3/2008 10:10:09 AMAPASS
Fire life safety completed. KR
BLD08-00502 FIRE-Final Inspection7/2/20087/3/20087/3/2008 9:32:42 AMPPASS
All corrections made per last inspection. KR