ELE12-00629
| ELE-Aging Inspection | 7/3/2013 | 7/3/2013 | 7/3/2013 3:29:24 PM | | DONE |
|
|
Called left message
|
ELE13-01309
| Final | 7/3/2013 | 7/3/2013 | 7/3/2013 3:20:37 PM | P | PASS |
|
|
For access please call Ed 1/2 hr prior to inspection. ###-#### >> Inspection requested via web by Terry Scott Final ok
|
ELE13-01705
| Permanent Service | 7/2/2013 | 7/3/2013 | 7/3/2013 2:45:38 PM | P | PASS |
|
|
clyde Phone #: ###-#### p/s u/g rec ok
|
ELE13-01694
| Rough-In Permanent Service | 7/3/2013 | 7/3/2013 | 7/3/2013 2:12:47 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Greg Traudt 300.4- Nail plates needed to protect wiring from physical damage in nook,quest bath, utility, and above AV panel. 300.4 NM cable secured less than 1 1/4" from surface of framing member in m. closet, above x-mas switch, several upstairs. 210.52 General purpose receptical required in study left as entered. 334.23 NM cable shall be protected from physical damage where run less than 6' from attic access. 314.4 Metal boxes shall be bonded and grounded per artical 250.
|
ELE13-01693
| Rough-In Permanent Service | 7/2/2013 | 7/3/2013 | 7/3/2013 1:13:38 PM | P | PASS |
|
|
troy Phone #: ###-#### p/s o/h n ok
|
ELE13-01707
| Electrical Rough-In | 7/2/2013 | 7/3/2013 | 7/3/2013 12:11:22 PM | A | CANC |
|
|
If not open lock box is 1931. Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Main permit has not been picked up yet, can not perform inspection until done
|
ELE13-00236
| Electrical Rough-In | 7/2/2013 | 7/3/2013 | 7/3/2013 11:52:26 AM | A | PASS |
|
|
need a ceiling cover Phone #: ###-#### >> Inspection requested via web by Karl Paige Ceiling rough in ok cover
|
ELE13-01617
| Electrical Rough-In | 7/2/2013 | 7/3/2013 | 7/3/2013 10:05:03 AM | A | NR |
|
|
don Phone #: ###-#### Service grounding and feeders not in, recepticals 18" minimum to bottom of boxes, NM support within 12" of junction boxes anddevice boxes.
|
ELE13-01617
| Conference | 7/2/2013 | 7/3/2013 | 7/3/2013 9:57:13 AM | A | DONE |
|
|
don Phone #: ###-#### Discussed receptical height in garage, NM support, service grounding and feeders, and owner would like to partial final garage when ready.
|
ELE13-01487
| Final | 7/2/2013 | 7/3/2013 | 7/3/2013 9:28:34 AM | A | FAIL |
|
|
Please call Asher Sears if any questions Phone #: ###-#### >> Inspection requested via web by brad williams 400.8 Split system, flexible cord shall not pass through wall. 406.11 In all areas listed in 210.52 all 15 and 20 amp120 volt recepticals shall be tamper resistant.
|
ELE13-01714
| Rough-In Permanent Service | 7/2/2013 | 7/3/2013 | 7/3/2013 9:05:29 AM | A | PASS |
|
|
Please call Jeff if you have any questions. Thanks Phone #: ###-#### >> Inspection requested via web by Brandon Blackham Rough in ok cover p/s o/h n ok
|
GCE13-00061
| GCE-Final | 7/2/2013 | 7/3/2013 | 7/3/2013 8:33:40 AM | A | PASS |
|
|
Terry ###-#### Call for access code Final ok
|
ELE13-01353
| Electrical Rough-In | 7/1/2013 | 7/3/2013 | 7/1/2013 3:57:44 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|