Inspections for the day of: Wednesday, July 3, 2013.
Number of inspections: 10
Percentage of inspections complete: 80 %
Percentage of inspections not complete: 20 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00257 INSP-Sprinkler Rough-in/Hydro6/27/20136/28/2013 A 
7:AM requested. (discussed with Troy) Phone #: ###-#### >> Inspection requested via web by Jason Babien
BLD12-02063 FIRE-Final Inspection6/27/20136/28/2013 A 
Steve Phone #: ###-####
FIR13-00020 INSP-Sprinkler Rough-in7/3/20137/3/20137/3/2013 3:28:42 PMPPASS
Vaulted ceiling area is ok to cover at 2018
FIR13-00204 INSP-Sprinkler Rough-in7/2/20137/3/20137/3/2013 3:25:47 PMACANC
Cancel per Nate
BLD13-00661 FIRE-Final Inspection7/2/20137/3/20137/3/2013 3:16:00 PMACANC
Cancel per Matt Hall Phone #: ###-####
FIR12-00717 INSP-Sprinkler Rough-in7/2/20137/3/20137/3/2013 1:58:52 PMAPASS
See the city approved plans for areas where the sprinkler rough-in passed.
FIR12-00695 INSP-Sprinkler Rough-in7/2/20137/3/20137/3/2013 10:24:25 AMAPART
See the city approved plans for rough-in inspection locations for today. Mostly passed but seismic restraint for the branchlines is missing is all location inspected today. Will need as-bults showing the new routing of the two 6" main in the service area. The car wash area piping size as installed does not match the approved plans.
FIR13-00017 INSP-Final Inspection7/2/20137/3/20137/3/2013 10:13:28 AMAPASS
Permit finaled
BLD13-01138 FIRE-Final Inspection7/2/20137/3/20137/3/2013 9:35:17 AMAPART
A temporary occupancy is approved by both scott and romeo until the access control and the high piled storage/racking is addressed.
BLD13-00978 FIRE-Final Inspection7/2/20137/3/20137/2/2013 2:32:37 PMAFAIL
Todays inspection actually turned into a more of a conference since the project related fire alarm permit is still in the REC status. Life safety will be ok to final when the project related fire alarm permit is finished, the emergency light in the stairwell is repaired and the correct hardware is installed on the restroom door. Mike wanted permission to begin installing office partitions and equipment so I deferred him to Scott for that approval. It does not appear that fire sprinkler work will be required.