Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00938 FIRE-Final Inspection7/3/20147/3/20147/3/2014 3:04:18 PMPPART
Completed re-inspection for previous correction items dated 6/30 related to apartments on the 2nd, 3rd and 4th floors. Provisions and adjustments finished with the exception of door closure at 212, exit discharge light at the main street side, outside waterflow bell not yet installed. Shell fire protection 1st floor pending necessary revisions per agreement on record. Temporary occupancy approved per R. Gervais.
FIR13-00689 INSP-Final Inspection7/3/20147/3/20147/3/2014 2:45:12 PMPPART
Inspection for scope of work at the 4th and 5th floors-. 5th floor plans need revised to indicate changes to core area- elevator lobby, stair lobby, and restrooms only (no corridor at this time). 4th floor sprinkler finishes complete. Need to install ceiling tile at both 4th and 5th floor riser closets.
FIR14-00121 INSP-Final Inspection7/3/20147/3/20147/3/2014 2:34:22 PMPPART
Completed walkthrough of finishes at the 3rd floor core scope of work. Need to add fire sprinkler protection for exposed 2" CPVC main at tie-in to apartment system.
FIR13-00608 INSP-Final Inspection7/3/20147/3/20147/3/2014 2:28:48 PMPPART
Walkthrough for fire sprinkler finishes at the 6th floor core area completed. *Need to provide as-builts for field modifications - added protection at a storage room.
FIR13-00440 INSP-Sprinkler Rough-in7/3/20147/3/20147/3/2014 2:26:38 PMPPART
Inspection for 2nd floor west lobby, north lobby and core area grid ceilings passed rough-in, okayed for cover. Need to provide upright protection at the exposed 2" CPVC feed main (apartments) located in the future office shell area.
BLD14-00414 FIRE-Final Inspection7/2/20147/3/20147/3/2014 2:21:06 PMAPART
Fire life safety inspection and evaluation at the kitchen and bakery areas completed. Items noted include; missing EM light at the exit discharge, post 2A10BC PFE, need to schedule fire alarm testing for occupant notification. As-builts for fire sprinkler modifications accepted. Request for temporary occupancy must be approved by fire prevention chief R. Gervais.
FIR14-00267 INSP-Final Inspection7/2/20147/3/20147/3/2014 2:11:44 PMAPASS
Fire alarm permit work passed functional testing and inspection after adjustment made while on site. Final approved.
FIR13-00658 INSP-Final Inspection7/2/20147/3/20147/3/2014 2:09:07 PMAPASS
Previous correction items verified for completion. Final inspection passed. Fire alarm permit finaled.