ELE17-01307
| Electrical Rough-In | 7/2/2017 | 7/3/2017 | 7/3/2017 11:59:16 AM | P | PASS |
|
|
Detached Garage - wall cover.
Late as possible please, Thank you, Lonnie Phone #: ###-#### Inspection requested via web by Lonnie Sorichta Detached garage ok cover
|
ELE17-01798
| Electrical Rough-In | 7/3/2017 | 7/3/2017 | 7/3/2017 11:58:51 AM | P | PASS |
|
|
Reinspect of failed ceiling inspect. Phone #: ###-#### Inspection requested via web by Richard Montgomery Corrections fixed suspended ceiling only ok cover
|
ELE17-01935
| Temporary Service | 6/30/2017 | 7/3/2017 | 7/3/2017 11:37:15 AM | A | CANC |
|
|
Temp construction power. Von is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen Need t/s permit for this.
|
ELE17-01174
| Final | 7/2/2017 | 7/3/2017 | 7/3/2017 10:01:04 AM | A | FAIL |
|
|
Garage code 1069 Phone #: ###-#### Inspection requested via web by Clay Jackson 110.25 lockout for dishwasher 210.12 AFCI protection for bedrooms(breaker in-op)
|
ELE17-01798
| Electrical Rough-In | 6/30/2017 | 7/3/2017 | 7/3/2017 9:29:47 AM | A | FAIL |
|
|
Ceiling grid inspection for front 2 offices and hallways. Lockbox code is 6790. Contact for job is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Support ENT unused openings shall be closed open j-box in entry
|
ELE17-02021
| Final | 6/26/2017 | 7/3/2017 | 7/3/2017 8:57:58 AM | A | PASS |
|
|
Please call Kathleen at ###-#### for access before arrival. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell Final for sprinkler receptacle ok
|
ELE17-01391
| Final | 6/30/2017 | 7/3/2017 | 7/3/2017 8:49:45 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Carport and parking lot lights ok
|