Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00787 INSP-Sprinkler Rough-in7/3/20177/3/20177/3/2017 1:14:23 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
BLD17-00214 FIRE-Final Inspection7/3/20177/3/20177/3/2017 12:08:34 PMPCANC
Duplicate inspection request.
BLD17-00214 FIRE-Final Inspection7/3/20177/3/20177/3/2017 11:49:43 AMAPART
Partial final for life fire safety complete, fire sprinkler inspection is complete (fire sprinkler head in mens restroom on level 2 needs replaced, seat and base of glass bulb are painted, sprinkler head in front of level 2 elevator needs replaced with an intermediate temperature fire sprinkler head, head is with 12 inches of heat register, landscaping needs to be trimmed back to provide access to the wall mounted PIV and FDC, items to be verified at final life fire safety inspection for level 1 area of work associated with this BLD permit) fire alarm complete for level 2 excluding elevator lobby smoke detector, operation will be verified at fire alarm completion for project, fire extinguishers are in place with current inspection tags, building does have a knox box mounted by main entry.
FIR17-00342 INSP-Final Inspection7/3/20177/3/20177/3/2017 11:37:31 AMPPART
Project is being worked in phases, fire alarm inspection for level 2 area of work complete, (level 1 as well as level 2 elevator lobby to be completed at a later date)
BLD15-02762 FIRE-Final Inspection6/30/20177/3/20177/3/2017 9:50:45 AMAPART
Final inspection for fire life safety is complete, permit can be finaled when FIR (FIR17-00343) permit for fire sprinkler work is issued, inspected and finaled.
NAF17-00039 INSP-Final6/30/20177/3/20177/3/2017 12:00:00 AMPDONE
Call prior to going Phone #: 2089853303 >> Inspection requested via mobile web by Mike Kroll
Per Jim Page fire alarm complete