Inspections for the day of: Tuesday, July 3, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02291 Electrical Rough-In7/2/20187/3/20187/3/2018 3:24:29 PMPPASS
CONTACT NAME : JOSH MANGUM
CEILING INSPECTION Phone #: ###-#### Inspection requested via web by Deb Gooden
Grid rough in ok cover
ELE18-01817 Electrical Rough-In7/3/20187/3/20187/3/2018 2:49:56 PMPPART
Job Foreman: Jay Karel Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
Listing confirmed on wall mount only, only able to verify disconnecting means on free standing sign
ELE17-03734 Conference7/2/20187/3/20187/3/2018 2:28:44 PMPFAIL
Requesting an inspection consultation to review the panel wall that failed inspection previously. Specifically requesting Daryl to review any possible solutions to this issue. Phone #: ###-#### Inspection requested via web by Clint Tate
As noted dedicated electrical space width and depth of panel board shall be clear for future expansion as per 110.26(E)(1)(a). As per conversation with Daryl DeGrange if only way to reconnect to pipes passing thru floor is in original area, only the amount permitted would be a 90 degree connector to leave dedicated electrical space.
ELE18-02470 Temporary Service7/2/20187/3/20187/3/2018 12:28:28 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
t/s u/g n ok
ELE18-02450 Rough-In Permanent Service7/2/20187/3/20187/3/2018 12:03:30 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE18-02358 Rough-In Permanent Service7/2/20187/3/20187/3/2018 12:02:36 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE18-00727 Final7/3/20187/3/20187/3/2018 11:33:50 AMPCANC
Temp final Phone #: ###-#### >> Inspection requested via web by Tom Jenkins Inspection cancelled from web by: Tom Jenkins
ELE18-00727 Final7/2/20187/3/20187/3/2018 11:26:48 AMAFAIL
Temp final Phone #: ###-#### Inspection requested via web by Tom Jenkins
210.8(B)- Other Than Dwelling Units. All single-phase receptacles rated 150 volts to ground or less, 50 amperes or less and threephase receptacles rated 150 volts to ground or less, 100 amperes or less installed in the following locations shall have ground-fault circuit-interrupter protection for personnel.
Multilple in kitchen area.
ELE18-01610 Final7/3/20187/3/20187/3/2018 10:40:10 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ron Zimmerman 210.8- All receptacles located in kitchen area shall have GFCI protection. Pizza oven, and 120 volt receptacles
ELE17-02862 Electrical Rough-In7/3/20187/3/20187/3/2018 10:28:04 AMAPASS
301 , 302 , 303 , 304 , 305 , 306 , 307 , 308 , 317 , 318 , 319 call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Rooms noted rough in ok cover
ELE18-02489 Electrical Rough-In7/2/20187/3/20187/3/2018 9:44:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed new permits needed for elevator. Electrical contractor has scope included in core and shell, elevator contractor will need seperate city and state permits.
Underground conduits for new gear in basement rough in ok cover.