Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02155 FIRE-Final Inspection7/3/20187/3/20187/5/2018 6:56:13 AMPPASS
No fire sprinkler modifications (Annual Inspection for fire sprinklers will be required NOV 2018), no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.

Michael Phone #: ###-####-please call with an approx meet time
FIR18-00119 INSP-Conference7/3/20187/3/20187/3/2018 12:58:06 PMPDONE
Fire conference complete for undeground supply.
FIR18-00119 INSP-Sprinkler Rough-in7/2/20187/3/20187/3/2018 12:57:01 PMPCANC
Request was for a conference on the underground, this request is cancelled.

Contact Brad Westbrook - ###-#### 30 Min prior to Insp. start, Brad needs this to be after 1PM if at all possible please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00021 INSP-Supply line flush7/2/20187/3/20187/3/2018 12:21:16 PMADONE
Underground main line flush complete.

George Jess is the contact for this underground Hydro and Flush. An appointment has been scheduled with Jim Page for 10AM and with Gus with Suez. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-03614 FIRE-Final Inspection7/2/20187/3/20187/3/2018 11:26:44 AMPFAIL
FIre sprinkler inspection is not complete, building is in no way ready for life fire safety inspection.

No personnel other that construction personnel inside of building until life fire safety inspection is complete.

Please call Phil when on site. Phone #: ###-#### Inspection requested via web by Philip Allen
FIR18-00196 INSP-Final Inspection7/3/20187/3/20187/3/2018 11:20:38 AMPCANC
Fire alarm system is for fire sprinkler riser monitoring and HVAC shutdown, fire sprinkler system is not ready so fire alarm inspection cannot be completed, this inspection request is cancelled.

Phone #: ###-#### Inspection requested via web by Ken Webster
BLD18-00593 FIRE-Final Inspection7/3/20187/3/20187/3/2018 10:57:03 AMPPASS
Fianl life fire safety inspection complete.

they close at 3:00 so would like you to go before then-if you can''t make it please call them to let them know-thanks Phone #: ###-####
BLD17-01763 FIRE-Final Inspection7/2/20187/3/20187/3/2018 10:38:38 AMAFAIL
Fire alarm permit FIR18-00124 needs to be finaled before life fire safety can be performed.

Fire finals Phone #: ###-#### Inspection requested via web by Mike Beeson
FIR18-00492 INSP-Sprinkler Rough-in7/2/20187/3/20187/3/2018 10:36:23 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00021 INSP-Sprinkler Rough-in/Hydro7/2/20187/3/20187/3/2018 10:11:15 AMADONE
Underground hydrostatic test witnessed, no pressure loss observed at contractor provided gauge.

George Jess is the contact for this Underground Hydro ; Flush. It has been discussed with Jim Page ; Gus with Suez. The appointment time is for 10AM., thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR17-00563 INSP-Final Inspection7/2/20187/3/20187/3/2018 9:44:17 AMAPASS
Final fire alarm inspection complete.

Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
BLD16-04392 FIRE-Final Inspection7/2/20187/3/20187/3/2018 9:01:09 AMAFAIL
Fire alarm permit FIR17-00230 needs to be inspected and finaled before life fire safety inspection can be completed.

call him if have any questions // Brandon Phone #: ###-####
FIR18-00390 INSP-Final Inspection7/2/20187/3/20187/3/2018 8:59:39 AMAFAIL
Tamper switches in vault are not hooked into the fire panel, wiring to vault is causing a ground fault.

Backflow valves are required to be electronically supervised.

Phone #: ###-#### Inspection requested via web by Nathan Price