Inspections for the day of: Wednesday, July 30, 2003.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02687 FIRE-Final Inspection7/28/20037/30/20037/30/2003 12:00:00 AMAFAIL
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need alarm map at panel; complete sprinkler (see sprinkler permit); exit signs on second floor; need one hour sprinkler room; knox box needed; 7/30/2003 11:48:16 AM
BLD03-00643 FIRE-Final Inspection7/28/20037/30/20037/30/2003 12:00:00 AMAFAIL
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need sprinkler head in closet and shell signed off 7/30/2003 11:41:58 AM
FIR03-00067 INSP-Sprinkler Rough-in/Hydro7/29/20037/30/20037/30/2003 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 7/29/2003 at 9:59:04 AM. Contact: ###-####. rescheduled for 7/31 7/30/2003 11:35:03 AM
FIR03-00088 INSP-Sprinkler Rough-in/Hydro7/29/20037/30/20037/30/2003 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 7/29/2003 at 10:00:42 AM. Contact: ###-####. talked to Mike B and he will reschedule for 7/31 7/30/2003 11:32:43 AM
FIR03-00089 INSP-Final Inspection7/30/20037/30/20037/30/2003 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Trent Bice 7/30/2003 11:34:43 AM
FIR03-00174 INSP-Final Inspection7/30/20037/30/20037/30/2003 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Trent Bice need one hour fire sprinkler riser room; ball drip on FDC; additional EQ on FDC; spare heads in head box; calc sticker; fire marshall tag on riser; sign on riser room door; escutcheons; some heads obstructed; straps needed; 7/30/2003 11:46:45 AM
FIR03-00200 INSP-Final Inspection7/30/20037/30/20037/30/2003 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Trent Bice need head in closet 7/30/2003 11:43:59 AM
FIR03-00215 INSP-Final Inspection7/30/20037/30/20037/30/2003 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Trent Bice need head in closet 7/30/2003 11:41:11 AM
FIR03-00261 INSP-Final Inspection7/30/20037/30/20037/30/2003 12:00:00 AMAPASS
FIR03-00408 INSP-Supply line flush7/30/20037/30/20037/30/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 7/30/2003 at 9:01:41 AM. Contact: ###-####.
FIR03-00070 INSP-Final Inspection7/29/20037/30/20037/30/2003 12:00:00 AMPFAIL
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore smoke/fire dampers need to comply with UBC 713 on how to operate the dampers with detectors; changes made to device numbers; this permit is being phased and NAC are not installed per plans 7/30/2003 4:49:58 PM
FIR03-00259 INSP-Final Inspection7/29/20037/30/20037/30/2003 12:00:00 AMPFAIL
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore smoke/fire dampers need to operate per IBC 907.10.10 7/30/2003 4:50:33 PM
FIR03-00368 INSP-Sprinkler Rough-in/Hydro7/29/20037/30/20037/30/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 7/29/2003 at 1:34:06 PM. Contact: ###-####. this portion of the permit is okay; hydro okay 7/30/2003 4:47:51 PM