FIR03-00233
| INSP-Final Inspection | 7/30/2003 | 7/30/2003 | 7/30/2003 12:00:00 AM | P | FAIL |
|
|
The main control vavle in the basement is not supervised by the fire alarm system. I could not verify any other possibly unsupervised valves. All valves to be supervised per review note #7. See NFPA 13 and NFPA 72. Provide inspection report. See review note #6. Provide canopies on pendants. 7/30/2003 12:28:42 PM
|
FIR03-00035
| INSP-Sprinkler Rough-in/Hydro | 7/30/2003 | 7/30/2003 | 7/30/2003 12:00:00 AM | P | PASS |
|
|
Underground hydro test is ok 7/30/2003 3:21:23 PM
|
BLD00-03672
| FIRE-Final Inspection | 7/30/2003 | 7/30/2003 | 7/30/2003 12:00:00 AM | P | FAIL |
|
|
sprinkler pendants are over spaced for an ordinary hazard occupancy. Provide ADA compliant door hardware on the restroom door and the service room door. Tag the fire extinguisher and repair the exit sign 7/30/2003 3:50:18 PM
|
FIR03-00246
| INSP-Conference | 7/30/2003 | 7/30/2003 | 7/30/2003 12:00:00 AM | P | FAIL |
|
|
I stopped at this project to verify that no fire alarm work was being performed and found conduit, boxes and fire alarm FPLP 12 guage wiring installed. A stop work order was issued to Quality Electrics (###-####) job foreman who's name is Alan. The actually man that installed the fire alarm, who also works for quality is Scott according to Alan.
|
BLD02-02339
| FIRE-Conference | 7/30/2003 | 7/30/2003 | 7/30/2003 12:00:00 AM | P | FAIL |
|
|
I stopped at this project to verify that no fire alarm work was being performed and found conduit, boxes and fire alarm FPLP 12 guage wiring installed. A stop work order was issued to Quality Electrics (###-####) job foreman who's name is Alan. The actually man that installed the fire alarm, who also works for quality is Scott according to Alan.
|