Inspections for the day of: Friday, July 30, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00236 INSP-Sprinkler Rough-in7/29/20047/30/20047/30/2004 12:00:00 AMPFAIL
Resubmit plans to city of boise for review of piping modifications. Do not cover pipe until PASS on re-inspection. Piping hangers and earthquake bracing shall be made to top where the loading was designed. See review note #71. Provide verification of single truss supports per review note #67. Provide verification of use of sidewinders supporting 4" main in 2x4 members. See review note #75. Provide verification that 2x4boards being used for trapeze meet nfpa 13 section 9. No items inspected other than those listed above. 7/30/2004 2:19:48 PM
BLD04-00695 FIRE-Final Inspection7/30/20047/30/20047/30/2004 12:00:00 AMPPASS
fire life safety finaled. 7/30/2004 11:09:30 AM
BLD04-00988 FIRE-Final Inspection7/30/20047/30/20047/30/2004 12:00:00 AMPFAIL
duct smoke detector needs to be mounted on the return not the supply and retested 7/30/2004 4:04:43 PM
BLD00-02965 FIRE-Final Inspection7/30/20047/30/20047/30/2004 12:00:00 AMPPASS
Life safety for the shell OK 7/30/2004 4:03:41 PM
FIR04-00236 INSP-Sprinkler Rough-in7/28/20047/30/20047/29/2004 9:01:16 AMACANC
Jobsite Contact: Nate; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley