ELE07-01395
| ELE-Aging Inspection | 7/30/2007 | 7/30/2007 | 8/2/2007 8:38:08 AM | | FAIL |
|
|
called left message 110.3(B) needs manufactures grd bar kit for suzi rating conn for GEC protect #8 GEC or install #6
|
ELE07-02651
| Permanent Service | 7/30/2007 | 7/30/2007 | 7/31/2007 3:05:26 PM | P | FAIL |
|
|
perm service/final. Questions pls call Mike @ ###-#### Phone #: ###-#### Internet Inspection Request from: Heather Packer
|
ELE07-02652
| Permanent Service | 7/30/2007 | 7/30/2007 | 7/30/2007 3:43:43 PM | P | FAIL |
|
|
perm service/final. For questions pls call Mike @ ###-#### Phone #: ###-#### Internet Inspection Request from: Heather Packer corr called needs ID stickers, prefab bld has state tag on it in mech rm but wiring is messed up panet is set over jbox behind it and access is through 3" chase nipple, grd rods shall be driven vertical if possible if not 45 degrees, if not possible then layed in trench 21/2ft deep and inspected before cover
|
ELE07-00447
| Final | 7/30/2007 | 7/30/2007 | 7/30/2007 2:25:39 PM | P | PASS |
|
|
glen Phone #: ###-#### ladies rest rm ok no card
|
ELE07-02535
| Conference | 7/30/2007 | 7/30/2007 | 7/30/2007 1:38:30 PM | P | DONE |
|
|
Steve- ###-#### conf. ok needs 11/4" holes and parallel, replace 2gang boxes broken clamps, single gang broken out KO, protect cables run horizontally no wall covering, provide switch point of acces to attic, complete all makeup, move 2 gang jbox for outside light
|
ELE07-02672
| Electrical Rough-In | 7/30/2007 | 7/30/2007 | 7/30/2007 12:55:12 PM | P | PART |
|
|
Spencer; Phone #: ###-#### Internet Inspection Request from: Darla Downs r/i ok S E corner walls only
|
ELE07-02562
| Electrical Rough-In | 7/27/2007 | 7/30/2007 | 7/30/2007 11:31:43 AM | A | NH |
|
|
tom/donna Phone #: ###-#### Pat talked with owner
|
ELE07-02651
| Final | 7/26/2007 | 7/30/2007 | 7/30/2007 11:31:13 AM | A | CANC |
|
|
All that was done was to put a meter on building - for questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer called needs p/s and check if prefab building has been inspected
|
ELE07-02652
| Final | 7/26/2007 | 7/30/2007 | 7/30/2007 11:30:15 AM | A | CANC |
|
|
Final - all that was done was putting a meter on building. For questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty. Phone #: ###-#### Internet Inspection Request from: Heather Packer called needs p/s and check if building is inspected note prefab building
|
ELE07-02549
| Permanent Service | 7/27/2007 | 7/30/2007 | 7/30/2007 11:27:55 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/27/2007 at 3:01:16 PM. Contact: ###-####. p/s u/g new ok meter
|
ELE07-02548
| Permanent Service | 7/27/2007 | 7/30/2007 | 7/30/2007 11:26:44 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/27/2007 at 2:58:27 PM. Contact: ###-####. p/s u/g new ok meter
|