Inspections for the day of: Monday, July 30, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01397 ELE-Aging Inspection7/30/20077/30/20078/3/2007 3:54:46 PM DONE
see final
ELE07-02547 Electrical Rough-In7/30/20077/30/20077/30/2007 4:05:46 PMPFAIL
Scheduled by a contractor via Hello! on 7/30/2007 at 5:08:10 AM. Contact: ###-####. met elect, told nec art 310.15 requires conduit spacing, they will fix and recall for another day
ELE07-02665 Temporary Service7/30/20077/30/20077/30/2007 3:52:10 PMPPASS
Reinspection for Temp. Power Pole. Steve Berry is the contact person. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw corr made, t/s u/g n ok
ELE07-02431 Conference7/30/20077/30/20077/30/2007 2:42:39 PMPDONE
steven - late afternoon - please call 1/2 hr prior to inspection Phone #: ###-#### talked about circuiting and number of outlets for addition
ELE07-02675 Electrical Rough-In7/30/20077/30/20077/30/2007 1:50:29 PMPPASS
electrician is Mike McCarrel Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok
ELE07-02675 Final7/30/20077/30/20077/30/2007 1:40:14 PMPPASS
electrician is Mike McCarrel Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok to final
ELE07-02615 Final7/26/20077/30/20077/30/2007 1:11:23 PMPNR
service inspection & final on pole barn Phone #: ###-#### Internet Inspection Request from: Miles Berry called, left message and notice, nh, nr, BCC all u/g shall be seen before cover, all makeup shall be seen before devices installed, shall have ri before final inspection, nec 250.52 shall use metal water pipe for gec,and 250.52(D)(2) shall augment water pipe with 2 ground rods and be inspected before cover
ELE07-02667 Conference7/27/20077/30/20077/30/2007 11:13:24 AMADONE
lawrence- ###-#### talked about ways to do wiring to outbuilding, loads and owner said he may get prices from contractor rather doing his own work
ELE07-00974 Electrical Rough-In7/25/20077/30/20077/30/2007 10:33:22 AMAPASS
DEAN Phone #: ###-#### ric garage ok
ELE07-01873 Electrical Rough-In7/27/20077/30/20077/30/2007 10:04:40 AMAPASS
tom Phone #: ###-#### master bath, bedroom and closet only ok to cover
ELE07-01544 Final7/27/20077/30/20077/30/2007 9:17:19 AMAPASS
trent Note: if need in call trent Phone #: ###-#### ok to final, signed occ card
ELE07-02666 Rough-In Permanent Service7/27/20077/30/20077/30/2007 8:33:11 AMAPASS
brandon Phone #: ###-#### called left message, left survey, nec 334.30 shall staple nm every 4 1/2' upstairs, 210.52(A)(2) shall provide outlets in 2' wall space,kitchen, ric ok, p/s u/g n ok
ELE07-02665 Temporary Service7/27/20077/30/20077/30/2007 7:53:44 AMAFAIL
This inspection is for a temp. pole. Contact name is Steve Berry
Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called left corr notice,fee due, nec 250.24(B) main bonding jumper shall connect the equip grounding conductor and service disconnect enclosure to grounded conductor, BCC shall post Boise City job id sticker
ELE07-00467 Electrical Rough-In7/27/20077/30/20077/30/2007 12:00:00 AMPCANC
some can lights have for the waiting room are on special order so we need a partial for the rest of the walls and ceiling so the job can continue forward Phone #: ###-#### Internet Inspection Request from: Curtis Dunham