Inspections for the day of: Monday, July 30, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00482 INSP-Sprinkler Rough-in/Hydro7/27/20077/30/20077/31/2007 5:39:16 PMPFAIL
Provide longitudinal bracing for the 2.5" main as discussed, need to fire caulk new penetrations in existing rated walls, need to install intermediate temp. heads at the stairway skylights.
BLD07-00842 FIRE-Final Inspection7/30/20077/30/20077/30/2007 5:13:15 PMPPASS
Fire life safety final inspection passed.
FIR07-00392 INSP-Final Inspection7/30/20077/30/20077/30/2007 5:11:26 PMPPASS
Corrections are complete, fire alarm permit finaled.
FIR07-00275 INSP-Final Inspection7/30/20077/30/20077/30/2007 4:17:01 PMPDEFR
Scheduled for 7/31.
FIR07-00517 INSP-Sprinkler Rough-in7/26/20077/30/20077/30/2007 3:54:35 PMAPART
UG fire supply line is approved for cover, depth of bury is okay provided infill meets grade at existing landscaping on either side, also need to provide method for seismic clearance where the riser passes through the floor slab.
BLD07-00978 FIRE-Final Inspection7/27/20077/30/20077/30/2007 3:36:17 PMAFAIL
Need to final the project related fire alarm permit, remove the manual thumbturn at the main entry/exit door, noted the existing fire sprinkler system is due for annual certification this month (overdue in two days).
FIR07-00486 INSP-Final Inspection7/27/20077/30/20077/30/2007 3:32:30 PMAPASS
Fire sprinkler work passed final inspection, permit finaled.
FIR07-00569 INSP-Final Inspection7/27/20077/30/20077/30/2007 3:30:57 PMAFAIL
No provision supplied to test duct detectors.
FIR07-00487 INSP-Final Inspection7/27/20077/30/20077/30/2007 3:28:13 PMAPASS
Fire sprinkler permit finaled.
BLD07-00979 FIRE-Final Inspection7/27/20077/30/20077/30/2007 3:27:08 PMAFAIL
Remove the manual thumbturn at the main entry/exit door, repair the exit sign at the main entry, EM lighting at the office area did not function.
BLD06-00717 FIRE-Final Inspection7/27/20077/30/20077/30/2007 2:35:41 PMAPASS
Life safety field inspection passed.
BLD06-00721 FIRE-Final Inspection7/27/20077/30/20077/30/2007 2:34:55 PMAPASS
Life safety inspection completed satisfactory, noted no signature card for occupancy request on site, (lost per contractor).
BLD07-00354 FIRE-Final Inspection7/27/20077/30/20077/30/2007 2:32:05 PMAPASS
Fire life safety inspection passed, noted one exit sign at the SE corner does not require the directional arrow (arrow to be blanked by contractor). Also discussed building D fire pump room c/n regarding NFPA 20 req.
FIR06-00728 INSP-Final Inspection7/27/20077/30/20077/30/2007 2:29:20 PMADEFR
To be completed in conjunction with the project related fire alarm permit final inspection.
BLD06-00688 FIRE-Final Inspection7/27/20077/30/20077/30/2007 2:28:08 PMANR
Still need fire alarm and sprinkler permit finals prior to life safety final.
BLD06-03043 FIRE-Final Inspection7/27/20077/30/20077/30/2007 2:27:09 PMAFAIL
Fire alarm work did not pass inspection, also need to install smoke seals at all three doors.
FIR07-00359 INSP-Final Inspection7/27/20077/30/20077/30/2007 2:25:24 PMAFAIL
Door holders failed to drop out upon fire alarm activation.