FIR07-00482
| INSP-Sprinkler Rough-in/Hydro | 7/27/2007 | 7/30/2007 | 7/31/2007 5:39:16 PM | P | FAIL |
|
|
Provide longitudinal bracing for the 2.5" main as discussed, need to fire caulk new penetrations in existing rated walls, need to install intermediate temp. heads at the stairway skylights.
|
BLD07-00842
| FIRE-Final Inspection | 7/30/2007 | 7/30/2007 | 7/30/2007 5:13:15 PM | P | PASS |
|
|
Fire life safety final inspection passed.
|
FIR07-00392
| INSP-Final Inspection | 7/30/2007 | 7/30/2007 | 7/30/2007 5:11:26 PM | P | PASS |
|
|
Corrections are complete, fire alarm permit finaled.
|
FIR07-00275
| INSP-Final Inspection | 7/30/2007 | 7/30/2007 | 7/30/2007 4:17:01 PM | P | DEFR |
|
|
Scheduled for 7/31.
|
FIR07-00517
| INSP-Sprinkler Rough-in | 7/26/2007 | 7/30/2007 | 7/30/2007 3:54:35 PM | A | PART |
|
|
UG fire supply line is approved for cover, depth of bury is okay provided infill meets grade at existing landscaping on either side, also need to provide method for seismic clearance where the riser passes through the floor slab.
|
BLD07-00978
| FIRE-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 3:36:17 PM | A | FAIL |
|
|
Need to final the project related fire alarm permit, remove the manual thumbturn at the main entry/exit door, noted the existing fire sprinkler system is due for annual certification this month (overdue in two days).
|
FIR07-00486
| INSP-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 3:32:30 PM | A | PASS |
|
|
Fire sprinkler work passed final inspection, permit finaled.
|
FIR07-00569
| INSP-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 3:30:57 PM | A | FAIL |
|
|
No provision supplied to test duct detectors.
|
FIR07-00487
| INSP-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 3:28:13 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD07-00979
| FIRE-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 3:27:08 PM | A | FAIL |
|
|
Remove the manual thumbturn at the main entry/exit door, repair the exit sign at the main entry, EM lighting at the office area did not function.
|
BLD06-00717
| FIRE-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 2:35:41 PM | A | PASS |
|
|
Life safety field inspection passed.
|
BLD06-00721
| FIRE-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 2:34:55 PM | A | PASS |
|
|
Life safety inspection completed satisfactory, noted no signature card for occupancy request on site, (lost per contractor).
|
BLD07-00354
| FIRE-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 2:32:05 PM | A | PASS |
|
|
Fire life safety inspection passed, noted one exit sign at the SE corner does not require the directional arrow (arrow to be blanked by contractor). Also discussed building D fire pump room c/n regarding NFPA 20 req.
|
FIR06-00728
| INSP-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 2:29:20 PM | A | DEFR |
|
|
To be completed in conjunction with the project related fire alarm permit final inspection.
|
BLD06-00688
| FIRE-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 2:28:08 PM | A | NR |
|
|
Still need fire alarm and sprinkler permit finals prior to life safety final.
|
BLD06-03043
| FIRE-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 2:27:09 PM | A | FAIL |
|
|
Fire alarm work did not pass inspection, also need to install smoke seals at all three doors.
|
FIR07-00359
| INSP-Final Inspection | 7/27/2007 | 7/30/2007 | 7/30/2007 2:25:24 PM | A | FAIL |
|
|
Door holders failed to drop out upon fire alarm activation.
|