Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00310 INSP-Final Inspection7/30/20087/30/20087/30/2008 4:50:40 PMPPASS
Fire alarm permit finaled.
FIR08-00209 INSP-Final Inspection7/30/20087/30/20087/30/2008 4:21:01 PMPPASS
Fire sprinkler permit finaled, repairs are complete.
FIR07-00606 INSP-Sprinkler Rough-in7/30/20087/30/20087/30/2008 4:20:17 PMPFAIL
Third reinspection for areas B and D plan sheet FP5 failed due to items including overspaced head at corridor A11, overspaced pendent at the girls locker room B40, missing branch line below the stairs at storage room B13 including three SSU heads, need intermediate temp. head adjacent to the supply register at girls room B38-noted per inspection completed 7/10, missing sprinkler coverage at the accessible mechanical room between mens B44 and womens B43 restrooms, notified general contractor to provide area separation between sprinklered and non-sprinklered areas at the storage room C228, one painted head replaced while on site. Ten item correction notice from yesterdays inspection is finished.
FIR08-00503 INSP-Sprinkler Rough-in7/30/20087/30/20087/30/2008 2:40:29 PMPFAIL
See approved plans for necessary corrections including six pendent heads which exceed min. separation, and hangers at three locations missing correct retaining strap attatchments.
FIR08-00508 INSP-Final Inspection7/29/20087/30/20087/30/2008 2:34:54 PMAFAIL
See fire code review notes item number seven for requirements.
FIR08-00461 INSP-Sprinkler Rough-in7/28/20087/30/20087/30/2008 2:33:14 PMAFAIL
Inspection for overhead fire sprinkler rough-in at the 7th floor failed due to changes in floorplan, piping layout, number, type and location of heads at several areas. Differences between field installation and approved plans are beyond what can normally be accepted on "as-built" drawings, will need to provide approved resubmittal plans including all changes. The installation appears acceptable, however documentation must be provided.
FIR08-00509 INSP-Final Inspection7/29/20087/30/20087/30/2008 11:34:43 AMAFAIL
Manual pull stations must be located no higher than 48" AFF to the operable part, see also review note #7 for details, functional testing delayed until repairs are finished.
FIR08-00518 INSP-Final Inspection7/29/20087/30/20087/30/2008 10:49:22 AMAPASS
Scope of work passed field inspection, minor field modifications accepted, permit finaled.
FIR08-00164 INSP-Sprinkler Rough-in/Hydro7/29/20087/30/20087/30/2008 10:25:51 AMAPART
UG fire supply line flush completed acceptable.
FIR08-00319 INSP-Sprinkler Rough-in7/29/20087/30/20087/30/2008 10:23:53 AMAPART
OH rough-in is approved for cover at the hard lid ceilings per red line plan annotations initialed with todays date at the school room #401.
FIR07-00606 INSP-Sprinkler Rough-in7/29/20087/30/20087/30/2008 8:20:17 AMACANC
Jerry is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
FIR08-00278 FIR-Aging Inspection7/30/20087/30/20087/30/2008 8:07:38 AM DONE
Work in progress, construction underway.