ELE10-01129
| Rough-In Permanent Service | 7/30/2010 | 7/30/2010 | 7/30/2010 3:47:26 PM | P | NR |
|
|
John Phone #: ###-#### met owner, ground rods not driven in or connnected, needs to add water pipe ground conductor, needs to separate neutral and ground bus in sub-panel, needs to provide abrasion protection for gec
|
ELE10-01656
| Rough-In Permanent Service | 7/30/2010 | 7/30/2010 | 7/30/2010 3:05:40 PM | P | PASS |
|
|
Any questions, please call Clay. Thank YOu. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ri ok, p/s o/h rec ok
|
ELE10-00959
| Rough-In Permanent Service | 7/30/2010 | 7/30/2010 | 7/30/2010 2:27:00 PM | P | CANC |
|
|
stu Phone #: ###-#### see final
|
ELE10-00959
| Final | 7/30/2010 | 7/30/2010 | 7/30/2010 2:26:51 PM | P | PASS |
|
|
stu Phone #: ###-#### met contractor, ok to final
|
ELE10-01663
| Permanent Service | 7/28/2010 | 7/30/2010 | 7/30/2010 1:20:42 PM | P | PASS |
|
|
Chad Phone #: ###-#### p/s o/h rec ok
|
ELE10-01621
| Electrical Rough-In | 7/29/2010 | 7/30/2010 | 7/30/2010 1:03:57 PM | P | PASS |
|
|
please call for door access code and I want to meet you there. Need a cover inspection Phone #: ###-#### >> Inspection requested via web by Steve Ruter ric ok
|
ELE10-00926
| Final | 7/27/2010 | 7/30/2010 | 7/30/2010 11:35:29 AM | A | PASS |
|
|
key bank logo and letters on south of bank Phone #: ###-#### >> Inspection requested via web by travis wilson ok
|
ELE10-01003
| Final | 7/27/2010 | 7/30/2010 | 7/30/2010 10:28:29 AM | A | PASS |
|
|
at&t letters Phone #: ###-#### >> Inspection requested via web by travis wilson ok
|
ELE10-01676
| Final | 7/29/2010 | 7/30/2010 | 7/30/2010 10:18:57 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left message, left correction notice, NEC 230.24(A) shall provide 8' clearance over roof surface for service conductors, 250.53(G) upper end of electrodes shall be flush with or below ground, 408.4 shall complete circuit schedules, note; corrections shall be made within 5 working days, advised that contractor shall call for p/s inspection
|
ELE10-01530
| Electrical Rough-In | 7/30/2010 | 7/30/2010 | 7/30/2010 9:59:33 AM | A | PASS |
|
|
Potting compound for spa light Phone #: ###-#### >> Inspection requested via web by Lynn Cable potting only ok
|
ELE09-00800
| Final | 7/29/2010 | 7/30/2010 | 7/30/2010 9:11:06 AM | A | PASS |
|
|
Herbert Phone #: ###-#### corrections made. ok to final
|
ELE10-01678
| Rough-In Permanent Service | 7/29/2010 | 7/30/2010 | 7/30/2010 8:35:40 AM | A | PASS |
|
|
Mike Phone #: ###-#### ri ok, p/s u/g n ok
|
ELE10-00923
| ELE-Aging Inspection | 7/30/2010 | 7/30/2010 | 7/30/2010 6:25:21 AM | | DONE |
|
|
suc
|
ELE08-02743
| ELE-Aging Inspection | 7/30/2010 | 7/30/2010 | 7/30/2010 6:24:36 AM | | DONE |
|
|
see doc expire
|
ELE08-02743
| DOC - Permit Expired | 7/30/2010 | 7/30/2010 | 7/30/2010 6:24:20 AM | A | PASS |
|
|
no activity
|
ELE08-02793
| ELE-Aging Inspection | 7/30/2010 | 7/30/2010 | 7/30/2010 6:22:51 AM | | DONE |
|
|
see final
|
ELE08-02793
| Final | 7/30/2010 | 7/30/2010 | 7/30/2010 6:22:38 AM | A | PASS |
|
|
ok
|