Inspections for the day of: Friday, July 30, 2010.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01129 Rough-In Permanent Service7/30/20107/30/20107/30/2010 3:47:26 PMPNR
John Phone #: ###-#### met owner, ground rods not driven in or connnected, needs to add water pipe ground conductor, needs to separate neutral and ground bus in sub-panel, needs to provide abrasion protection for gec
ELE10-01656 Rough-In Permanent Service7/30/20107/30/20107/30/2010 3:05:40 PMPPASS
Any questions, please call Clay. Thank YOu. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ri ok, p/s o/h rec ok
ELE10-00959 Rough-In Permanent Service7/30/20107/30/20107/30/2010 2:27:00 PMPCANC
stu Phone #: ###-#### see final
ELE10-00959 Final7/30/20107/30/20107/30/2010 2:26:51 PMPPASS
stu Phone #: ###-#### met contractor, ok to final
ELE10-01663 Permanent Service7/28/20107/30/20107/30/2010 1:20:42 PMPPASS
Chad Phone #: ###-#### p/s o/h rec ok
ELE10-01621 Electrical Rough-In7/29/20107/30/20107/30/2010 1:03:57 PMPPASS
please call for door access code and I want to meet you there. Need a cover inspection Phone #: ###-#### >> Inspection requested via web by Steve Ruter ric ok
ELE10-00926 Final7/27/20107/30/20107/30/2010 11:35:29 AMAPASS
key bank logo and letters on south of bank Phone #: ###-#### >> Inspection requested via web by travis wilson ok
ELE10-01003 Final7/27/20107/30/20107/30/2010 10:28:29 AMAPASS
at&t letters Phone #: ###-#### >> Inspection requested via web by travis wilson ok
ELE10-01676 Final7/29/20107/30/20107/30/2010 10:18:57 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left message, left correction notice, NEC 230.24(A) shall provide 8' clearance over roof surface for service conductors, 250.53(G) upper end of electrodes shall be flush with or below ground, 408.4 shall complete circuit schedules, note; corrections shall be made within 5 working days, advised that contractor shall call for p/s inspection
ELE10-01530 Electrical Rough-In7/30/20107/30/20107/30/2010 9:59:33 AMAPASS
Potting compound for spa light Phone #: ###-#### >> Inspection requested via web by Lynn Cable potting only ok
ELE09-00800 Final7/29/20107/30/20107/30/2010 9:11:06 AMAPASS
Herbert Phone #: ###-#### corrections made. ok to final
ELE10-01678 Rough-In Permanent Service7/29/20107/30/20107/30/2010 8:35:40 AMAPASS
Mike Phone #: ###-#### ri ok, p/s u/g n ok
ELE10-00923 ELE-Aging Inspection7/30/20107/30/20107/30/2010 6:25:21 AM DONE
suc
ELE08-02743 ELE-Aging Inspection7/30/20107/30/20107/30/2010 6:24:36 AM DONE
see doc expire
ELE08-02743 DOC - Permit Expired7/30/20107/30/20107/30/2010 6:24:20 AMAPASS
no activity
ELE08-02793 ELE-Aging Inspection7/30/20107/30/20107/30/2010 6:22:51 AM DONE
see final
ELE08-02793 Final7/30/20107/30/20107/30/2010 6:22:38 AMAPASS
ok